NINFA 24 MCS
50
GB
cod. 3540F611 - 05/2007 (Rev. 00)
Service Menu
The card Service Menu is accessed by turning the selector (detail 3 - fig. 1) to RESET for 10 seconds and then to
(winter) or
(summer). Use the heating knob (detail 1 - fig. 1) to select “tS”, “In”, “Hi” or “rE”. “tS” means Transparent
Parameters Menu, “In” means Information Menu, “Hi” means History Menu, “rE” means History Menu Reset. After se-
lecting the Menu, to access it turn the selector (detail 3 - fig. 1) to RESET for 1 second and then to
(winter) or
(summer).
“tS” - Transparent Parameters Menu
The card has 24 transparent parameters modifiable also from Remote Timer Control (Service Menu):
Table. 2
With the heating knob (detail 1 - fig. 1) it is possible to scroll the list of parameters, in increasing or decreasing order
respectively. To modify the value of a parameter just turn the DHW knob (detail 2 - fig. 1): the modification will be auto-
matically saved.
To go back to the Service Menu turn the selector (detail 3 - fig. 1) to RESET for 1 second and then to
(winter) or
(summer). To exit the card Service Menu turn the selector (detail 3 - fig. 1) to RESET for 10 seconds and then to
(winter) or
(summer).
Remote
Control
Card
Description of Transparent Parameters
Range
Default
01
P01
Type of gas selection
0=Natural Gas, 1=LPG
0=Natural Gas
02
P02
Not used
Not modifiable
1
03
P03
Absolute min. power
0-100%
0%
04
P04
Lighting power
0-60%
50%
05
P05
Not used
Not modifiable
0
06
P06
Heating system train
1-20°C/min
5°C/min
07
P07
Post Circulation heating system
pump
0-20 minutes
6 min
08
P08
Heating wait time
0-10 minutes
2 minutes
09
P09
Max. heating power
0-100%
100%
10
P10
Pump operation
0=Post Circulation
1=Continuous
0=Post Circulation
11
P11
Pump switching off temperature during Post Cir-
culation
0-100°C
33°C
12
P12
Max. user setpoint in heating
31-85°C
85°C
13
P13
Post Circulation DHW circuit pump
0-255 seconds
30 seconds
14
P14
DHW circuit wait time
0-255 seconds
120 seconds
15
P15
Max. power in hot water production
0-100%
100%
16
P16
Max. user setpoint in hot water production
55-65°C
55°C
17
P17
Comfort activation temperature
0-80°C
40°C
18
P18
Comfort deactivation hysteresis
0-30°C
20°C
19
P19
Burner turning off in hot water production
0=Fixed, 1=Linked to setp., 2= For
solar system1, 3= For solar system2
1=Linked to setp.
20
P20
Not used
Not modifiable
4
21
P21
Not used
Not modifiable
8
22
P22
Not used
Not modifiable
0
23
P23
Not used
Not modifiable
0
24
P24
Mains Voltage Frequency
0=50Hz, 1=60Hz
0=50Hz
Summary of Contents for NINFA 24 MCS
Page 155: ...NINFA 24 MCS 155 EL cod 3540F611 05 2007 Rev 00 5 1 9 1 2 6 1 9 1 3 Comfort Comfort 6 1 9 1 4...
Page 157: ...NINFA 24 MCS 157 EL cod 3540F611 05 2007 Rev 00 3 1 8 1 4 3 1 9 3 1 1 1 30 C 85 C 45 C 10...
Page 172: ...NINFA 24 MCS 172 EL cod 3540F611 05 2007 Rev 00 3 2 B sez 4 4 sez 1 3 sez 4 4 3 3 1 bar A...
Page 175: ...NINFA 24 MCS 175 EL cod 3540F611 05 2007 Rev 00 F37 F39 A41 F42 F43 H2O F50...
Page 182: ......
Page 183: ......