61
3.1
HEAT MODE
Enable or disable the heating mode
1
0
1
1
/
3.2
t_T4_FRESH_H
The refresh time of climate related curves for heating
mode
0.5
0.5
6
0.5
hours
3.3
T4HMAX
The maximum ambient operating temperature for heating
mode
25
20
35
1
℃
3.4
T4HMIN
The minimum ambient operating temperature for heating
mode
-15
-25
30
1
℃
3.5
dT1SH
The temperature difference for starting the unit (T1)
5
2
20
1
℃
3.8
T1SetH1
The setting temperature 1 of climate related curves for
heating mode
35
25
65
1
℃
3.9
T1SetH2
The setting temperature 2 of climate related curves for
heating mode
28
25
65
1
℃
3.10
T4H1
The ambient temperature 1 of climate related curves for
heating mode
-5
-25
35
1
℃
3.11
T4H2
The ambient temperature 2 of climate related curves for
heating mode
7
-25
35
1
℃
3.12
ZONE1 H-EMISSION
The type of zone1 end for heating mode
:
0=FCU(fan coil
unit)
,
1=RAD.(radiator)
,
2=FLH(floor heating)
1
0
2
1
/
3.13
ZONE2 H-EMISSION
The type of zone2 end for heating mode
:
0=FCU(fan coil
unit)
,
1=RAD.(radiator)
,
2=FLH(floor heating)
2
0
2
1
/
3.14
t_DELAY_PUMP
2
0.5
20
0.5
MIN
4.1
T4AUTOCMIN
The minimum operating ambient temperature for cooling in
auto mode
25
20
29
1
℃
4.2
T4AUTOHMAX
The maximum operating ambient temperature for heating
in auto mode
17
10
17
1
℃
5.1
WATER FLOW TEMP.
Enable or disable the WATER FLOW TEMP.:0=NON,1=YES
1
0
1
1
/
5.2
ROOM TEMP.
Enable or disable the ROOM TEMP.:0=NON,1=YES
0
0
1
1
/
5.3
DOUBLE ZONE
Enable or disable the ROOM THERMOSTAT DOUBLE
ZONE:0=NON,1=YES
0
0
1
1
/
7.1
dT1_IBH_ON
The temperature difference betw een T1S and T1 for
starting the backup heater.
5
2
10
1
℃
7.2
t_IBH_DELAY
The time that the compressor has run before the first
backup heater turns on
30
15
120
5
MIN
7.3
T4_IBH_ON
The ambient temperature for starting the backup heater
-5
-15
30
1
℃
7.7
IBH_LOCATE
IBH/AHS installation location PIPE LOOP=0; BUFFER TANK=1
0
0
0
0
℃
7.8
P_IBH1
Power input of IBH1
0
0
20
0.5
kW
7.9
P_IBH2
Power input of IBH2
0
0
20
0.5
kW
7.10
P_TBH
Power input of TBH
2
0
20
0.5
kW
7.4
dT1_AHS_ON
The temperature difference betw een T1S and T1 for
turning the additional heating source on
5
2
20
1
℃
7.5
t_AHS_DELAY
The time that the compressor has run before starting the
additional heating source
30
5
120
5
MIN
7.6
T4_AHS_ON
The ambient temperature for starting the additional
heating source
-5
-15
30
1
℃
8.1
T1S_H.A_H
The target outlet w ater temperature for space heating
w hen in holiday aw ay mode
25
20
25
1
℃
8.2
T5S_H.A_DHW
The target outlet w ater temperature for domestic hot
w ater heating w hen in holiday aw ay mode
25
20
25
1
℃
12.1
PREHEATING FOR
FLOOR T1S
The setting temperature of outlet w ater during first
preheating for floor
25
25
35
1
℃
12.3
t_FIRSTFH
The time last for preheating floor
72
48
96
12
HOUR
The style of room thermostat
:
0=NON,1=MODE
SET,2=ONE ZONE,3=DOUBLE ZONE
6.1
ROOM THERMOSTAT
0
0
3
1
/
3.7
t_INTERVAL_HEAT
the start time interval of the compressor in HEAT mode
5
5
5
1
MIN
The temperature difference for starting the unit (Ta)
2
1
10
1
℃
3.6
dTSH
The delay time for water pump to stop after the
compressor stops
EN
IDOLA M 3.2
04÷16T
CAUTION
34
Ethylene Glycol and Propylene Glycol are TOXIC
WARNING
NOTE
During filling, it might not be possible to remove all air in the system. Remaining air will be removed through the
automatic air purge valves during the first operating hours of the system. Topping up the water afterwards might be
required.
The water pressure will vary depending on the water temperature (higher pressure at higher water temperature).
However, at all times water pressure should remain above 0.3 bar to avoid air entering the circuit.
The unit might drain-off too much water through the pressure relief valve.
Water quality should be complied with EN 98/83 EC Directives.
Detailed water quality condition can be found in EN 98/83 EC Directives.
Connect the water supply to the filling valve and open the valve.
Make sure the automatic air purge valve is open (at least 2 turns).
Fill with water pressure of approximately 2.0 bar. Remove air in the circuit as much as possible using the air purge
valves. Air in the water circuit could lead to malfunction of the backup electric heater.
9.5 Filling water
Do not fasten the black plastic cover on
the vent valve at the topside of the unit
when the system is running. Open air
purge valve, turn anticlockWise at least
2 full turns to release air from the
system.
CounterclockWise rotation, remove the flow switch.
Drying the flow switch completely.
When the unit is not running for a long time, make sure the unit is powered on all the time. If you want to cut off the
power, the water in the system pipe needs to be drained clean to avoid the unit and pipeline system being damaged by
freezing. Also the power of the unit needs to be cut off after water in the system is drained off.