39
Voltage
(V)
Hz
Min.
(V)
Max.
(V)
MCA
(A)
TOCA
(A)
MFA
(A)
MSC
(A)
RLA
(A)
KW
FLA
(A)
Outdoor Unit
Power Current
Compressor
OFM
1
1
1
1
14
18
-
13.50
0.10
0.50
264
25
220-240 50
198
-
14.50
0.17
1.50
16
19
264
25
220-240 50
198
-
17
19
15.50
0.17
1.50
264
198
25
220-240 50
12
25
-
0.10
0.50
220-240 50
198
264
18
11.50
System
6kW
4kW
8kW
10kW
-
25
30
23.50
0.17
1.50
264
198
35
220-240 50
12kW
-
26
30
24.50
0.17
1.50
264
198
35
220-240 50
14kW
1
-
27
30
25.50
0.17
1.50
264
198
35
220-240 50
16kW
-
10
14
9.15
0.17
1.50
456
342
16
380-415 50
12kW 3-PH
1
-
11
14
10.15
0.17
1.50
456
342
16
380-415 50
14kW 3-PH
-
12
14
11.15
0.17
1.50
456
342
16
380-415 50
16kW 3-PH
Table 9-2
Rated current
of appliance:
(
A
)
Nominal cross-sectional area (mm )
2
Flexible cords
Cable for fixed wiring
Table 9-1
≤
3 0.5 and 0.75 1 and 2.5
>
3 and
≤
6
0.75 and 1 1 and 2.5
>
6 and
≤
10
1 and 1.5 1 and 2.5
>
10 and
≤
16
1.5 and 2.5 1.5 and 4
>
16 and
≤
25
2.5 and 4 2.5 and 6
>
25 and
≤
32
4 and 6 4 and 10
>
32 and
≤
50
6 and 10 6 and 16
>
50 and
≤
63
10 and 16 10 and 25
1-phase 4-16kW standard and 3-phase 12-16kW standard
Voltage
(V)
Hz
Min.
(V)
Max.
(V)
MCA
(A)
TOCA
(A)
MFA
(A)
MSC
(A)
RLA
(A)
KW
FLA
(A)
Outdoor Unit
Power Current
Compressor
OFM
1
1
1
1
27
31
-
13.50
0.10
0.50
264
38
220-240 50
198
-
14.50
0.17
1.50
29
32
264
38
220-240 50
198
-
30
32
15.50
0.17
1.50
264
198
38
220-240 50
25
38
-
0.10
0.50
220-240 50
198
264
31
11.50
System
6kW
4kW
8kW
10kW
-
38
43
23.50
0.17
1.50
264
198
48
220-240 50
12kW
-
39
43
24.50
0.17
1.50
264
198
48
220-240 50
14kW
1
-
40
43
25.50
0.17
1.50
264
198
48
220-240 50
16kW
-
23
27
9.15
0.17
1.50
456
342
29
380-415 50
12kW 3-PH
1
-
24
27
10.15
0.17
1.50
456
342
29
380-415 50
14kW 3-PH
-
25
27
11.15
0.17
1.50
456
342
29
380-415 50
16kW 3-PH
1-phase 4-16kW and 3-phase 12-16kW standard with backup heater 3kW
Voltage
(V)
Hz
Min.
(V)
Max.
(V)
MCA
(A)
TOCA
(A)
MFA
(A)
MSC
(A)
RLA
(A)
KW
FLA
(A)
Outdoor Unit
Power Current
Compressor
OFM
1
1
1
-
14.50
0.17
1.50
29
32
456
38
380-415 50
342
-
30
32
15.50
0.17
1.50
456
342
38
380-415 50
System
8kW
10kW
-
38
43
23.50
0.17
1.50
456
342
48
380-415 50
12kW
-
39
43
24.50
0.17
1.50
456
342
48
380-415 50
14kW
1
-
40
43
25.50
0.17
1.50
456
342
48
380-415 50
16kW
-
23
27
9.15
0.17
1.50
456
342
29
380-415 50
12kW 3-PH
1
-
24
27
10.15
0.17
1.50
456
342
29
380-415 50
14kW 3-PH
-
25
27
11.15
0.17
1.50
456
342
29
380-415 50
16kW 3-PH
1-phase 8-16kW and 3-phase 12-16kW standard with backup heater 9kW
EN
IDOLA M 3.2
04÷16T
CAUTION
34
Ethylene Glycol and Propylene Glycol are TOXIC
WARNING
NOTE
During filling, it might not be possible to remove all air in the system. Remaining air will be removed through the
automatic air purge valves during the first operating hours of the system. Topping up the water afterwards might be
required.
The water pressure will vary depending on the water temperature (higher pressure at higher water temperature).
However, at all times water pressure should remain above 0.3 bar to avoid air entering the circuit.
The unit might drain-off too much water through the pressure relief valve.
Water quality should be complied with EN 98/83 EC Directives.
Detailed water quality condition can be found in EN 98/83 EC Directives.
Connect the water supply to the filling valve and open the valve.
Make sure the automatic air purge valve is open (at least 2 turns).
Fill with water pressure of approximately 2.0 bar. Remove air in the circuit as much as possible using the air purge
valves. Air in the water circuit could lead to malfunction of the backup electric heater.
9.5 Filling water
Do not fasten the black plastic cover on
the vent valve at the topside of the unit
when the system is running. Open air
purge valve, turn anticlockWise at least
2 full turns to release air from the
system.
CounterclockWise rotation, remove the flow switch.
Drying the flow switch completely.
When the unit is not running for a long time, make sure the unit is powered on all the time. If you want to cut off the
power, the water in the system pipe needs to be drained clean to avoid the unit and pipeline system being damaged by
freezing. Also the power of the unit needs to be cut off after water in the system is drained off.