60
10.5.18 Setting parameters
Order number
Code
State
Default
Minumum
Maximum
Setting
interval
Unit
1.1
DHW MODE
Enable or disable the DHW mode:0=NON,1=YES
1
0
1
1
/
1.2
DISINFECT
Enable or disable the disinfect mode:0=NON,1=YES
1
0
1
1
/
1.3
DHW PRIORITY
Enable or disable the DHW priority mode:0=NON,1=YES
1
0
1
1
/
1.4
PUMP_D
Enable or disable the DHW pump mode:0=NON,1=YES
0
0
1
1
/
1.5
DHW PRIORITY TIME SET Enable or disable the DHW priority time set:0=NON,1=YES
0
0
1
1
/
1.6
dT5_ON
The temperature difference for starting the heat pump
10
1
30
1
℃
1.7
dT1S5
The difference value between Twout and T5 in DHW mode
10
5
40
1
℃
1.8
T4DHWMAX
The maximum ambient temperature that the heat pump
can operate at for domestic water heating
43
35
43
1
℃
1.9
T4DHWMIN
The minimum ambient temperature that the heat pump can
operate for domestic water heating
-10
-25
30
1
℃
1.10
t_INTERVAL_DHW
the start time interval of the compressor in DHW mode.
5
5
5
1
MIN
1.11
dT5_TBH_ OFF
the temperature difference between T5 and T5S that
turns the booster heater off.
5
0
10
1
℃
1.12
T4_TBH_ON
the highest outdoor temperature the TBH can operate.
5
-5
50
1
℃
1.13
t_TBH_DELAY
the time that the compressor has run before starting the
booster heater
30
0
240
5
MIN
1.14
T5S_DISINFECT
the target temperature of water in the domestic hot water
tank in the DISINFECT function.
65
60
70
1
℃
1.15
t_DI_HIGHTEMP.
the time that the highest temperature of water in the
domestic hot water tank in the DISINFECT function will
last
15
5
60
5
MIN
1.16
t_DI_MAX
the maximum time that disinfection will last
210
90
300
5
MIN
1.17
t_DHWHP_RESTRICT
he operation time for the space heating/cooling operation.
30
10
600
5
MIN
1.18
t_DHWHP_MAX
the maximum continuous working period of the heat pump
in DHW PRIORITY mode.
90
10
600
5
MIN
1.20
PUMP_D RUNNING TIME the certain time that the DHW pump will keep running for
5
5
120
1
MIN
1.19
PUMP_D TIMER
Enable or disable the DHW pump run as timed and keeps
running for PUMP RUNNING TIME:0=NON,1=YES
1
0
1
1
/
1.21
PUMP_D DISINFECT RUN
Enable or disable the DHW pump operate when the unit is
in disinfect mode and T5
≥
T5S_DI-2:0=NON,1=YES
1
0
1
1
/
2.1
COOL MODE
Enable or disable the cooling mode:0=NON,1=YES
1
0
1
1
/
2.2
t_T4_FRESH_C
The refresh time of climate related curves for cooling
mode
0.5
0.5
6
0.5
hours
2.3
T4CMAX
The highest ambient operation temperature for cooling
mode
52
35
52
1
℃
2.4
T4CMIN
the lowest ambient operating temperature for cooling
mode
10
-5
25
1
℃
2.5
dT1SC
the temperature difference for starting the heat pump(T1)
5
2
10
1
℃
2.6
dTSC
the temperature difference for starting the heat pump(Ta)
2
1
10
1
℃
2.8
T1SetC1
The setting temperature 1 of climate related curves for
cooling mode.
5
10
5
25
1
MIN
2.9
T1SetC2
The setting temperature 2 of climate related curves for
cooling mode.
16
5
25
1
℃
2.10
T4C1
The ambient temperature 1 of climate related curves for
cooling mode.
35
-5
46
1
℃
2.11
T4C2
The ambient temperature 2 of climate related curves for
cooling mode.
25
-5
46
1
℃
2.12
ZONE1 C-EMISSION
The type of zone1 end for cooling mode
:
0=FCU(fan coil
unit)
,
1=RAD.(radiator)
,
2=FLH(floor heating)
0
0
2
1
/
2.13
ZONE2 C-EMISSION
The type of zone2 end for cooling mode
:
0=FCU(fan coil
unit)
,
1=RAD.(radiator)
,
2=FLH(floor heating)
0
0
2
1
/
The parameters related to this chapter are shown in the table below.
2.7
t_INTERVAL_COOL
the start time interval of the compressor in COOL mode
5
5
1
℃
EN
IDOLA M 3.2
04÷16T
CAUTION
34
Ethylene Glycol and Propylene Glycol are TOXIC
WARNING
NOTE
During filling, it might not be possible to remove all air in the system. Remaining air will be removed through the
automatic air purge valves during the first operating hours of the system. Topping up the water afterwards might be
required.
The water pressure will vary depending on the water temperature (higher pressure at higher water temperature).
However, at all times water pressure should remain above 0.3 bar to avoid air entering the circuit.
The unit might drain-off too much water through the pressure relief valve.
Water quality should be complied with EN 98/83 EC Directives.
Detailed water quality condition can be found in EN 98/83 EC Directives.
Connect the water supply to the filling valve and open the valve.
Make sure the automatic air purge valve is open (at least 2 turns).
Fill with water pressure of approximately 2.0 bar. Remove air in the circuit as much as possible using the air purge
valves. Air in the water circuit could lead to malfunction of the backup electric heater.
9.5 Filling water
Do not fasten the black plastic cover on
the vent valve at the topside of the unit
when the system is running. Open air
purge valve, turn anticlockWise at least
2 full turns to release air from the
system.
CounterclockWise rotation, remove the flow switch.
Drying the flow switch completely.
When the unit is not running for a long time, make sure the unit is powered on all the time. If you want to cut off the
power, the water in the system pipe needs to be drained clean to avoid the unit and pipeline system being damaged by
freezing. Also the power of the unit needs to be cut off after water in the system is drained off.
Cod. 3QE47850 - Rev. 00 - 03/2022