27
UK
NOZZLE CHOICE
Nozzle
GPH
PUMP PRESSURE bar
CAP
ACITY
(kg/h)
POWER (kW)
7
8
9
10
11
12
13
14
0,40
1,24
1,32
1,40
1,47
1,54
1,61
1,68
1,75
14,71
15,66
16,60
17,43
18,26
19,09
19,92
20,75
0,50
1,45
1,57
1,65
1,73
1,81
1,89
1,97
2,05
16,62
18,62
19,57
20,51
21,50
22,42
23,36
24,31
0,60
1,81
1,93
2,01
2,23
2,32
2,42
2,52
2,64
21,46
22,89
23,83
26,44
27,51
28,70
29,88
31,31
0,65
2,00
2,12
2,25
2,40
2,63
2,74
2,80
2,91
23,72
25,14
26,68
28,46
31,19
32,49
33,21
34,51
0,75
2,35
2,50
2,65
2,80
2,95
3,07
3,20
3,33
27,87
29,65
31,43
33,21
34,99
36,41
37,95
39,49
0,85
2,75
2,92
3,10
3,27
3,45
3,60
3,75
3,90
32,62
34,63
36,76
38,78
40,92
42,69
44,47
46,25
1,00
3,10
3,30
3,50
3,67
3,85
4,02
4,20
4,38
36,76
39,13
41,51
43,52
45,66
47,67
48,72
51,95
1,25
3,85
4,12
4,40
4,61
4,82
5,03
5,25
5,46
45,66
48,86
52,18
54,67
57,16
59,65
62,26
64,75
1,50
4,60
4,95
5,30
5,55
5,80
6,05
6,30
6,55
54,55
58,70
62,85
65,82
68,78
71,75
74,72
77,68
1,75
5,40
5,69
6,18
6,46
6,75
7,06
7,38
7,96
64,04
67,48
73,29
76,61
80,05
83,73
87,53
91,20
2,00
6,20
6,63
7,07
7,43
7,75
8,10
8,42
8,80
73,53
78,63
83,85
88,12
91,92
96,07
98,87
104,37
2,25
6,95
7,46
7,96
8,38
8,70
9,12
9,50
9,90
82,42
88,47
94,41
99,39
103,17
108,17
112,67
117,42
2,50
7,75
8,30
8,82
9,28
9,67
10,17
-
-
91,92
98,44
104,61
110,06
114,70
120,62
-
-
The choice depends on the capacity of the boiler chamber bearing in mind that Light Oil has
a heating value (P.C.I.) of 10200 kcal/kg. The scheme shows the range or consumption, in
kG/H and kW, of light Oil in relation to the nozzle size (in GPH) and to pump pressure (in
bar). For burners with preheater the effective range levels are approximately 10% lower than
those shown in the scheme.
Example: Chamber power 29 kW.
With a pump pressure of 12 bar the nearest level is 28,70 kW which corresponds to a nozzle of
0,60GPH. In cases where the right nozzle is not available it is possible, within the limits shown
in the paragraph “PUMP PRESSURE ADJUSTMENT” to alter the pump pressure in order to
obtain the desired capacity.