3.9.6 Making the load connections
8V to 100V Models
Refer to Fig.3-6 for connection of the load wires to the power supply bus-bars and to Fig.3-7 for
mounting the bus-bars shield to the chassis.
WARNING
Hazardous voltages may exist at the outputs and the load connections
when using a power supply with a rated output greater than 40V. To
protect personnel against accidental contact with hazardous voltages,
ensure that the load and its connections have no accessible live parts.
Ensure that the load wiring insulation rating is greater than or equal to
the maximum output voltage of the power supply.
CAUTION
Ensure that the load wiring mounting hardware does not short the output
terminals. Heavy connecting cables must have some form of strain relief
to prevent loosening the connections or bending the bus-bars.