INSTALLATION, OPERATING AND TROUBLESHOOTING INSTRUCTIONS FOR MODEL E12
Page 10 of 20
TABLE #1 - E12 HEAT LOSSES (SINGLE PHASE) (based on 75% eff. at rated load)
DC AMPS-DC VOLTS
WATTS IN WATTS OUT WATTS LOST
BTU/HR.
3- 24V
106
79
26
91
6- 24V
211
158
53
182
10-24V
352
264
88
303
15-24V
528
396
132
455
20-24V
704
528
176
607
25-24V
880
660
220
759
30-24V
1056
792
264
910
35-24V
1232
924
308
1062
3-48V
211
158
53
182
6-48V
422
317
106
364
10-48V
704
528
176
607
15-48V
1056
792
264
910
20-48V
1408
1056
352
1214
30-48V
2112
1584
528
1821
35-48V
2816
2112
704
2428
3-130V
572
429
143
493
6-130V
1144
858
286
986
10-130V
1907
1430
477
1644
15-130V
2860
2145
715
2466
20-130V
3813
2860
953
3287
30-130V
5720
4290
1430
4931
35-130V
7627
5720
1907
6575