background image

INSTALLATION, OPERATING AND TROUBLESHOOTING INSTRUCTIONS FOR MODEL E12 

Page 7 of 20 

 

 

 

 

 

AUTOMATIC CHARGE CONTROLS (TYPE AC41) 

The  charge  rate  is  completely  controlled  by  the  saturable  reactor  and  sensing  control  (AC41).    The 

battery voltage is sensed by the AC41 Control Panel.  An op-amp conducts into the base of a transistor 

and the transistor operates to shunt the saturating coil of the reactor.  When the battery is discharged, 

the battery voltage is low and the reactor saturating coil saturates the reactor.  The impedance change of 

the reactor due to the core saturating shifts more voltage to the primary of the transformer which in turn 

increases the induced voltage in the secondary of the transformer, thus, increasing the charge rate to 

maximum rated output.  When the battery voltage reaches it float voltage, the control begins to operate 

to reduce the charge rate.  The op-amp begins to conduct into the transistor and begins to shunt the 

current  from  the  saturating  coil  to  the  reactor.    The  reactor  begins  to  de-saturate  increasing  the 

impedance, and the voltage to the transformer primary begins to drop, thus decreasing the output. 

 

AC LINE COMPENSATION 

The  float  charger  has  a  specially  designed  transformer/reactor  combination,  which  inherently 

compensates for variations in the incoming AC power.  The impedance balance of the transformer/reactor 

combination compensates for a line voltage variation of + 10% of the nominal AC voltage specified on 

the nameplate. 

 

AUTOMATIC CURRENT LIMITING 

The float charger will charge to its maximum current capacity and begin to current limit if overloaded.  

The automatic current limiting feature limits the output of the charger to a maximum of 105% rated load.  

The control panel is preset and factory adjusted to the required current limiting.  The current limiting is 

accomplished  by  limiting  the  saturating  current  to  the  reactor,  thus,  controlling  the  maximum  current 

output of the unit. 

 

AC POWER FAILURE 

A power failure relay is provided to disconnect the automatic control from the battery and, therefore, 

limit  the  drain  on  the  battery.    One  (1)  set  of  normally  open  and  closed  contacts  from  this  relay  is 

connected to terminals for connection to a remote power failure alarm.  The charger will automatically 

resume charging upon return of AC power. 

 

ADJUSTMENTS/MAINTENANCE 

The charger is factory tested and preset so that no field adjustments are necessary.  Potentiometers are 

provided for adjusting the float and equalizing voltages to the required levels.  Because of the stable, 

rugged, and static design of this unit, very little maintenance is required.  Occasional blowing out of dust 

and tightening of connections are the only maintenance requirements.  

 

Float / Equalize lights indicate the charge mode of the rectifier. 

 

FILTERING E12 UNITS 

Additional  filtering  is  provided  on  E12  units.    Standard  filtering  is  100  MV-RMS  when  connected  to  a 

battery with an amp hour capacity of four (4) times the capacity of the charger at rated output.  

Summary of Contents for CONSTAVOLT E12

Page 1: ... FLOAT BATTERY CHARGER Including optional accessories 18B Digital Combination Alarm Package And 010 AC and DC Circuit Breakers ECN DATE CPN109298 17650 11 07 16816 6 05 106 BRADROCK DRIVE DES PLAINES IL 60018 847 299 1188 FAX 847 299 3061 ISSUE DATE 16390 08 04 INSTRUCTION DRAWING NUMBER P25 LE12 1 ...

Page 2: ...PERATION FOR THIS REASON IT IS OF UTMOST IMPORTANCE THAT EACH TIME BEFORE USING THIS UNIT YOU READ THIS MANUAL AND FOLLOW THE INSTRUCTIONS EXACTLY To reduce risk of battery explosion follow these instructions and those published by the battery manufacturer and manufacturer of any equipment you intend to use in the vicinity of the battery Review cautionary marking on all products PERSONAL PRECAUTIO...

Page 3: ...from the battery will corrode and damage equipment A sealed maintenance free or valve regulated lead acid VRLA may be placed below this equipment Never allow the battery electrolyte to drip on this unit when reading the specific gravity or filling the battery Do not operate this unit in a closed in area or restrict ventilation in any way Do not set any battery on top of this unit DC CONNECTION PRE...

Page 4: ... a copy of the claim to La Marche Mfg may void warranty service for any physical damages reported for repair HANDLING WARNING Equipment can be very heavy and top heavy Use adequate manpower or equipment for handling Until the equipment is securely mounted care must be used to prevent the equipment from being accidentally tipped over NOMENCLATURE PLATES Each piece of La Marche Mfg Equipment shipped...

Page 5: ...tery cables charger output and relay rack terminals Connect the proper battery cable to the ground bar or battery charger output terminal Energize the power supply by turning on the units AC breaker This will charge the capacitors inside the power supply and eliminate heavy arcing when the remaining battery cable is connected After approximately one 1 minute turn off the power supply and immediate...

Page 6: ...ge Check the battery manufacturers specification for the proper float equalize voltage setting and equalize cycle When a battery is discharged or standing idle the battery voltage will be less than the float or equalize voltage Therefore when the charger is put into operation it will immediately begin to charge the battery The charger will charge the battery at its rated output to a predetermined ...

Page 7: ...e voltage variation of 10 of the nominal AC voltage specified on the nameplate AUTOMATIC CURRENT LIMITING The float charger will charge to its maximum current capacity and begin to current limit if overloaded The automatic current limiting feature limits the output of the charger to a maximum of 105 rated load The control panel is preset and factory adjusted to the required current limiting The cu...

Page 8: ...52620 400 400000 1750 1750000 2 66360 500 500000 2000 2000000 DENOTES ALL SIZES LARGER THAN 0000 ARE EXPRESSED IN MCM TABLE OF CONVENTIONS CMA Cross section of wire in circular MIL area A Ultimate drain in amperes LF Conductor loop feet MAX AMP Maximum allowable amperes for given voltage drop AVD Allowable voltage drop K 11 1 Constant factor for commercial TW type copper wire KS5482 01 17 4 for al...

Page 9: ... use the Power Cable Formula to determine wire size WIRE GAUGE TABLE WIRE SIZE EQUIPMENT REQUIREMENT GROUNDING FUSE CUSTOMER CONDUCTOR SIZE CONNECTION MINIMUM 1 14 14 3 14 14 4 14 14 5 14 14 6 14 14 10 14 14 15 12 12 20 12 12 25 10 12 30 10 10 35 8 10 40 8 10 45 8 10 50 8 10 60 6 10 70 6 8 80 4 8 90 4 8 100 4 8 110 2 6 125 2 6 130 2 6 WIRE SIZE EQUIPMENT REQUIREMENT GROUNDING FUSE CUSTOMER CONDUCT...

Page 10: ...15 24V 528 396 132 455 20 24V 704 528 176 607 25 24V 880 660 220 759 30 24V 1056 792 264 910 35 24V 1232 924 308 1062 3 48V 211 158 53 182 6 48V 422 317 106 364 10 48V 704 528 176 607 15 48V 1056 792 264 910 20 48V 1408 1056 352 1214 30 48V 2112 1584 528 1821 35 48V 2816 2112 704 2428 3 130V 572 429 143 493 6 130V 1144 858 286 986 10 130V 1907 1430 477 1644 15 130V 2860 2145 715 2466 20 130V 3813 ...

Page 11: ...tentiometers of both units until the load is shared equally at the desired float voltage 7 After a short period of time one unit may assume more of the load Readjust the lower output charger so the current is half the load 8 Once properly set the charger should load share when the load is varied from no load to full load 9 Since there is no interconnecting circuitry and the units are completely is...

Page 12: ... output fuse DC output amps when measuring the DC output voltage with battery and load connected to rectifier TROUBLESHOOTING CONSTAVOLT BATTERY CHARGER AND POWER SUPPLIES SYMPTOM POSSIBLE CAUSE PROCEDURE Open AC input fuse 1 Incorrect AC input 1 Compare AC input voltage with voltage on unit s nameplate 2 Shorted diodes 2 See Troubleshooting and Diode Replacement Sheet Open DC output fuse 1 Defect...

Page 13: ...e Again note the ohmmeter reading If the diode is good the meter will indicate a high resistance in one direction and a low resistance with the leads reversed If the diode is shorted the meter will read full scale or 0 resistance with the leads in either direction If the diode is open the ohmmeter needle will not indicate or show infinite resistance indicating an open circuit with the ohmmeter lea...

Page 14: ...heck front panel meters and alarms for accuracy 4th Year REPEAT ABOVE WITH THE ADDITION OF 1 Check relay contacts for pitting or corrosion 2 Check capacitors for leakage 7th Year REPEAT ALL WITH THE ADDITION OF 1 Filter resonating capacitors and control relays should be replaced 10th Year REPEAT ALL WITH THE ADDITION OF except replacing capacitors and control relays they should be replaced every 7...

Page 15: ...borne by purchaser 2 If the purchaser elects not to return the equipment to the factory and wishes a factory service representative to make adjustments and or repairs at the equipment location La Marche s field service labor rates will apply A purchase order to cover the labor and transportation cost is required prior to the deployment of the service representative In accepting delivery of the equ...

Page 16: ...e Factory if the defect s were due to faulty material or workmanship credit will be issued 2 The equipment can be returned to the La Marche factory to have the inspections parts replacements and testing performed by factory personnel Should it be necessary to return a piece of equipment or parts to the factory the customer or sales representative must obtain authorization from the factory If upon ...

Page 17: ...rm 2 with light High DC Voltage Alarm with light and 2 Sets of Form C contacts Low DC Current Alarm with light and 2 Sets of Form C contacts High DC Voltage Shutdown with light and 1 Sets of Form C contacts Reset pushbutton Equalize select mode switch Selectable Ground Detection circuit with 1 set of Form C contacts Yes ACTIVE No DISABLED The low DC volts low current high DC voltage alarms the equ...

Page 18: ...y will read NO followed by SAVE The display and LED will change every five seconds After going through one cycle the display will return to the normal mode The alarm settings Timer Mode or Equalize Time can be reset while their function is active i e LED is blinking by using the equalize select mode switch Pushing the switch to up will raise the setting while pushing the equalize select mode switc...

Page 19: ...g After the equalize period the timer will wait for another 7 days and then restart MODE 2 DISPLAY indicates P02 This mode of operation automatically starts an equalize cycle every 14 days The length of this cycle is again determined by the timer setting After the equalize period the timer will wait for another 14 days and then restart MODE 3 DISPLAY indicates P03 This mode of operation automatica...

Page 20: ...TION OPERATING AND TROUBLESHOOTING INSTRUCTIONS FOR MODEL E12 Page 20 of 20 AC AND DC CIRCUIT BREAKERS 010 OPTION Description Single Pole AC Breaker 120Vac Two Pole AC Breaker 208 OR 240Vac Two Pole DC Breaker ...

Reviews: