background image

Thank you for having chosen an LAE electronic product. Before installing the instrument, please read this instruction booklet carefully in order to
ensure safe installation and optimum performance.

1. INSTALLATION

1.1

The MP1-15, size 77x35x77 mm (WxHxD), is inserted into the panel through a hole measuring 71x29 mm and is fixed by means

of the suitable clips, by pressing gently. If fitted, check that the rubber gasket adheres to the panel perfectly, in order to prevent debris
and moisture infiltration to the back of the instrument.

1.2

The instrument should work with room temperatures between -10°.. +50°C and relative humidity between 15%.. 80% inclusive.

Supply voltage, switched powers and connection set-up should scrupulously comply with the indications given on the container. To
reduce the effects of electromagnetic disturbance, keep the sensor and signal cables well separate from the power wires.

1.3

The sensor T1 measures the air temperature and activates in the thermostat control cycle; it should be placed inside the appliance

in a point that truly represents the temperature of the stored product. If fitted and enabled, (T2=YES), the sensor T2 measures the
evaporator temperature, and should be placed where there is the maximum formation of frost.

CAUTION

: should the relays have to switch a heavy load frequently, it is advisable to contact the manufacturer for indications on the lifetime of

the contacts.
Whenever products must be kept within very severe specifications or the products have considerable value, the use of a second instrument is
recommended, which activates upon or warns of any malfunction.

2. OPERATING MODES

Upon switching on, just the central line (autotest) appears on the display for approximately three seconds and the subsequent
indications depend on the operating status of the controller. TABLE 1 gives the indications associated with the various states, whereas
the symbols appearing below are explained in TABLE 2.

2.1 S

TANDBY

.

If button 

is pressed for 3 seconds, it allows the MP1-15 to be put on a standby, or to resume output control (with

parameter 

SB

=YES only). An 

indication on the display shows that the outputs are off permanently.

2.2 N

ORMAL

.

During normal operation, the display shows the temperature measured by probe T1, presented in the most appropriate

manner. Through parameter 

SCL

you select the display range according to the table below:

OFF

0/I

INSTRUCTIONS FOR INSTALLATION AND USE.

MP1

0LMP1001EN

S

TANDBY

N

ORMAL

I

NFO

M

ENU

I

NFO

D

ATA

S

ETUP

M

ENU

P

ARAMETER

V

ALUE

OFF

-19

T1

-20

SCL

1°C

Not

Product   

Air

Display scale

Operating

Temper. (sim.)

temperature

DEF

T2

-25

SPL

-25

Defrost

Evaporator Minimum 

temperature

setpoint

REC

- - -

- - - 

SPH

-18

Recovery after 

....   

Maximum 

defrost

setpoint

HI 

TLO

-1.9

- - - 

- - - 

High temperature  

Min. stored 

....  

alarm

temperature

- - -  

CND

15

- - - 

- - - 

....

Condenser clean 

....

cycle

E1

LOC

NO

- - - 

- - - 

Faulty T1 probe

Locked keypad

TABLE 1

SCL

1°C (only with INP=SN4)

2°C

°F

R

ANGE

-50/-9.9.. +19.9/+80

-50.. +120

-55.. +240

Reviews: