The temperature measured by probe T1 may be corrected with a fixed offset by assigning a value other than 0 to the parameter 

OS1

.

Also probe T2 may be corrected with a fixed offset, in this case parameter 

OS2

. Additionally, prior to display, the temperature is

treated by an algorithm that allows the simulation of a thermal mass directly proportional to the 

SIM

value. The result is a reduction in

the fluctuation of the displayed value.

2.3 INFO 

MENU

. Pressing the button 

and releasing it immediately activates the information selection menu. From this menu you

can display the instantaneous temperatures T1 and T2; the maximum (THI) and minimum (TLO) stored temperature; the total operating
time of the condenser since its last cleaning (CND) and the keypad status (LOC). The information to be displayed can be selected
sequentially, by pressing 

repeatedly or quickly via the buttons 

and 

to scroll through the menu. Exit from the info menu is by

pressing button 

or automatic after 6 seconds of not using the keypad.

In the 

operating mode it’s also possible to reset the recordings THI and TLO and the hour counter CND by pressing buttons 

+

simultaneously while the value is displayed. 

2.4 S

ETPOINT

.

The setpoint value is displayed by pressing and keeping button 

pressed for at least half second. The value is

programmed by pressing buttons 

or 

within the minimum limit 

SPL

and the maximum limit 

SPH

. When the button is

released, the newly programmed value is stored. The actual setpoint, minimum and maximum setpoint limits depend on the selection
active when the operation is performed.

2.5 K

EYPAD LOCK

.

The keypad lock avoids undesired, potentially dangerous operations, which might be attempted when the

controllers is operating in a public place. In the INFO mode, through the buttons 

and 

it’s possible to assign YES or NO to the

parameter 

LOC

. With LOC=YES all keypad commands are inhibited. To resume normal operation of keypad, adjust setting so that

LOC=NO.

2.6 D

EFROSTING

By assigning a value grater than 0 to the parameter 

DDY

, during defrost the indication 

is displayed instead

of the temperature. In this case, after defrost and for the time programmed in DDY, the display indication 

shows that the normal

thermostatic cycle is being resumed.

2.7 A

LARM

An anomaly in the operation is displayed through the lighting up of an abbreviation showing its cause: 

high/low

alarm temperature in the cabinet, 

door open, 

periodic condenser cleaning, 

fault of probe T1 / T2.

2.8 S

ETUP

.

The setup is accessed by pressing the buttons  +

in succession and keeping them pressed simultaneously for 5

seconds. The available parameters appear in TABLE 2 as shown below.

3. CONFIGURATION

The controller is configured for the system to be controlled by programming the operating parameters, that is, through the setup (see par.
2.8). In SETUP, press button 

to pass from one parameter to the next, and press button 

to go back. To display the value of a

parameter press 

, to modify it press buttons 

or  

simultaneously. Exit from the setup is by pressing button 

or automatic

after 30 seconds of not using the keypad.

Table 2

0/I

i

set

i

set

i

set

0/I

E2

E1

CL

DO

LO

HI

REC

DEF

i

set

i

set

0/I

i

set

i

set

0/I

i

set

i

set

INSTRUCTIONS FOR INSTALLATION AND USE.

Par. Adjustment

Function

Sect.

SCL

1°C/2°C/°F

Readout scale

2.2

SPL

-50.. SPH [°]

Minimum temperature set point

2.4

SPH

SPL.. +120 [°]

Maximum temperature set point

2.4

SP

SPL.. SPH [°]

Effective temperature set point

4.1

C-H

REF/HEA

Refrigerating/Heating selection

4.1

HYS

+1.. +100 [°]

Thermostat hysteresis

4.1

CRT

0.. 30 [min]

Compressor rest time

4.1

CT1

0.. 30 [min]

Compressor run with sensor T1 failure

4.2

CT2

0.. 30 [min]

Compressor stop with sensor T1 failure

4.2

CSD

0.. 30 [min]

Compressor stop delay from door opening 

4.3

DFR

0.. 24

Defrost frequency /24h

5.1

DLI

-50.. +120 [°]

Defrost end temperature

5.3

DTO

1.. 120 [min]

Maximum defrosting duration

5.3

DTY

OFF/ELE/GAS

Defrost type

5.2

DRN

0.. 30 [min]

Drain down time

5.2

DDY

0.. 60 [min]

Defrost display control

2.6

FID

YES/NO

Fans active during defrost

6.3

FDD

-50.. +120 [°]

Fan re-start delay temperature

6.4

FTC

YES/NO

Evaporator fan timed control

6.1

FT1

0.. 180 [sec]

Fan stop delay

6.1

FT2

0.. 30 [min]

Timed fan stop

6.1

FT3

0.. 30 [min]

Timed fan run

6.1

Par.

Adjustment

Function

Sect.

ATL

-120.. 0 [°]

Low alarm differential

7.1

ATH 

0.. +120 [°]

High alarm differential

7.1

ATD 

0.. 120 [min]

Alarm temperature delay

7.1

ADO  

0.. 30 [min]

Door alarm delay

7.2

ACC  

0.. 52 [weeks]

Periodic condenser cleaning

7.3

IISM

NON/MAN

2nd set switching mode

9.1

IISL

-50.. IISH [°]

Minimum 2nd temperature set

2.4

IISH

IISL.. +120 [°]

Maximum 2nd temperature set

2.4

IISP

IISL.. IISH [°]

Effective 2nd temperature set

4.1

IIHY

+1.. +100 [°]

Hysteresis of 2nd temperature set

4.1

IIDF

0.. 24

Defrost frequency /24h In mode 2

5.1

IIFT

YES/NO

Evaporator fan timed control in mode 2

6.1

SB

YES/NO

Button enabling

2.1

DS

YES/NO

Door switch enabling

7.2

INP

SN4/ST1

NTC/PTC probe selection

9.2

OS1

-125.. +125 [°]

probe T1 offset

2.2

T2

YES/NO

Probe T2 enabling

1.3

OS2

-125.. +125 [°]

Probe T2 offset

2.2

TLD

1.. 30 [min]

Delay for min./max. temperature storage

8

SIM

0.. 100

Display slowdown

2.2

ADR

0.. 255

Not active

- -

0/I