Output Frequency when fail
Q is an Integer number from 0 to 9. The units is Hz.
LLL
Output load percent when fail
LLL is Maximum of W% or VA%.
VA% is a percent of power.
W% is a percent of maximum active power.
CCC.C
Output current when fail
C is an Integer ranging from 0 to 9. The units is A.
HHH.H
Positive BUS voltage when
fail
H is an Integer ranging from 0 to 9. The units is V.
NNN.N
Negative BUS voltage when
fail
N is an Integer ranging from 0 to 9. The units is V.
BBB.B
Battery voltage
B is an Integer ranging from 0 to 9. The units is V.
TTT.T
Max Temperature of the
detecting pointers
T is an integer ranging from 0 to 9. The units is °C
b7b6b5b4b
3b2b1b0
Ups status
b7: DC to DC is on
b6: AC to DC is on
b5: Inverter is on
b4: Reserved
(
always 0
)
b3: Reserved
(
always 0
)
b2: output relay is on
b1: Reserved
(
always 0
)
b0: Reserved
(
always 0
)
Example:
Computer: QWS<Enter>
UPS:
(01 208.3 50.0 000.0 0.0 000 000.0 300.0 290.0 245.5 028.0 01000000<cr>
Meanings: The fault is BUS soft start failure
,
and when fail, the UPS status is:
Input voltage is 208.3V.
Input frequency is 50.0HZ.
Output voltage is 0V.
Output frequency is 0HZ
Load percent is 0%
Output current is 0A
Positive Bus voltage is 300.0V
Negative Bus voltage is 290.0V
Battery voltage is 245.5V.
Temperature is 28.0
℃
The AC to DC is on, inverter is off, output relay is off.