BA_060 Rev 1B6 Pressure transmitter PASCAL CS
Page 15/20
6.4.3
Decimal-point setting (
dEcP
)
You can set a fixed decimal point or allow the system to compute the best position for the
decimal point.
Display
Designation
Description
Automatic
The decimal point is set so that the decimal
places are fully used
No decimal place
One decimal place
Two decimal places
Three decimal places
Return
Return to "
dEcP
"
Table 10: Parameter list for setting the decimal point
Please note that when the decimal point is set as “fixed”, the decimal point will shift to the
right if there are insufficient digits to the left of the decimal point. If, for example, the dis-
play is set to use two decimal places and the measured value is 110 mbar, the display will
show “
110.0
”.
6.5 Switch-point Menue (
SP
)
The switch-point menue contains the functions for setting the first and second switch-point.
The menue items vary, depending on whether you select a hysteresis or frame function.
Independently from the output function you can define switching delays.
Display
Designation
Description
Switch-point
Switch-point in the selected measuring unit
Reset-point
Reset-point in the selected unit
Delay switch
Output delay at the switch point
Delay reset
Output delay at the reset point
Output function
Configuring the output (normally open / normally
closed, hysteresis / frame)
Menue items for second switch point
Return
Return to "
SP
"
Table 11: Menue items for a switching output with hysteresis function
The switch-point (SP) must be between the upper range limit (URL) and the reset-point.
The reset-point (rP) must be between the lower range limit (LRL) and the switch-point. The
minimum distance between switch-point and reset-point (minimal hysteresis) is 0.5% of the
measuring range.