BA_060 Rev 1B6 Pressure transmitter PASCAL CS
Page 12/20
As an example the steps needed to change the unit from bar to PSI are shown below.
> 2 s
> 1 s
Figure 11: Operator actions for changing the measuring unit
6.3.2
Correcting the Zero Point (
tlr
)
You can correct the zero point by up to ±20% of the measuring range with the "teach lower
range" menue item (
tlr
). When the menue item is selected the entry points to "
-rEt-
".
To trigger the function go to "
YES
" with one of the arrow buttons and confirm with the mid-
dle button. This extra step prevents any unintentional zero shift while navigating the
menue.
With the final confirmation, the applied pressure is stored as zero point. "
donE
" appears on
the display to confirm that the zero point has been adjusted and the device switches back
to the menue item "Teach Lower Range" " (
tlr
).
Display
Designation
Description
Return
Return to „
tlr
“
Confirm (yes)
Setting the applied pressure as the zero point
(0 bar)
Table 6: Parameter list for correcting the zero point
The steps needed to adjust the zero point are shown below (starting from display mode).
> 2 s
> 1 s
Figure 12: Operator actions for correcting the zero point