BA_072_2020-02_10.00 Pressure transmitter PASCAL Ci4
Page 4/28
3.4 Mounting the Remote Display
Optionally you can mount the display and control unit away from the measuring point in an
additional housing. The back plate of the housing is universally suitable for wall mounting
or pipe mounting for pipe diameters from 30 – 64 mm. For pipe mounting, you can order
the corresponding U-bolts from LABOM.
For best EMC protection, only use the included cable.
If you ordered the remote display together with the device, the assembly has been com-
pleted in the factory. You only need to route the cable and mount the housing with the re-
mote display.
If you have received the remote display as a retrofit kit, proceed as follows:
1. Unmount the front cover and the display unit from the PASCAL Ci4 (see 4.2).
2. Replace them with the adapter piece (round part with M12 socket) and front cover,
which were screwed onto the remote display housing for shipment. Do not forget to
connect the cable on the back with the display connector on the CPU module.
3. The cable may be shortened to on-site requirements. Colour codes on the terminals
indicate which wire should be connected to which terminal (see Figure 2).
4. Mount the remote display housing using the mounting holes to a wall, a pipe or another
suitable location.
5. Plug the M12 connector of the cable into the socket of the adapter piece.
6. Now connect the cable on the display module with the corresponding connector on the
terminal board in the remote housing and insert the display module in the same man-
ner as for the device itself (see 4.2).
7. The last step is to close the remote housing with the display cover that was previously
on the device.
Colour codes
BN/BR: Brown
WH/WS: White
BU/BL: Blue
BK/SW: Black
Figure 2: Connection of the remote display housing
This modification can be performed during operation. We do recommend, however, to
switch off the device during the modification.