LAARS Heating Systems
Page 8
Figure 3. Combustion Air and Vent Through Side Wall.
U.S. Installations (see note 1)
Canadian Installations (see note 2)
A=
Clearance above grade, veranda, porch,
12 inches (30 cm)
12 inches (30 cm)
deck, or balcony
B=
Clearance to window or door that may be
4 feet (1.2 m) below or to side of opening; 36 inches (91 cm)
opened
1 foot (30 cm) above opening
C=
Clearance to permanently closed window
See note 4
See note 5
D=
Vertical clearance to ventilated soffit located
above the terminal within a horizontal
See note 4
See note 5
distance of 2 feet (61cm) from the center line
of the terminal
E=
Clearance to unventilated soffit
See note 4
See note 5
F=
Clearance to outside corner
See note 4
See note 5
G=
Clearance to inside corner
See note 4
See note 5
H=
Clearance to each side of center line
3 feet (91 cm) within a height 15 feet above
extended above meter/regulator assembly See note 4
the meter/regulator assembly
I=
Clearance to service regulator vent outlet
See note 4
3 feet (91 cm)
J=
Clearance to nonmechanical air supply inlet
to building or the combustion air inlet to
4 feet (1.2 m) below or to side of opening; 36 inches (91 cm)
any other appliance
1 foot (30 cm) above opening
K=
Clearance to a mechanical air supply inlet
3 feet (91 cm) above if within 10 feet (3 m) 6 feet (1.83 m)
horizontally
Vent termination not allowed in this location for
Vent termination not allowed in this location category IV appliances. A vent shall not
L=
Clearance above paved sidewalk or paved for category IV appliances. For Category III terminate directly above a sidewalk or paved
driveway located on public property
appliances, vent must terminate at least 7 driveway that is located between two single
feet (2.13m) above the sidewalk or driveway. family dwellings and serves both dwellings.
For Category III appliances that do not violate
the previous condition, vent must terminate at
least 7 feet (2.13m) above the sidewalk or
driveway.
M=
Clearance under veranda, porch, deck,
See note 4
12 inches (30 cm) (see note 3)
or balcony
Notes:
1. In accordance with the current ANSI Z223.1 / NFPA 54 National Fuel Gas Code.
2. In accordance with the current CAN/CGA-B149 Installation Codes.
3. Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor.
4. For clearances not specified in ANSI Z223.1 / NFPA 54, clearance is in accordance with local installation codes and the requirements of the
gas supplier.
5. For clearances not specified in CAN/CGA-B149, clearance is in accordance with local installation codes and the requirements of the gas
supplier.
Summary of Contents for Rheos RHCH
Page 28: ...LAARS Heating Systems Page 28 Figure 20 Wiring Diagram Model 1200 Codes B and E...
Page 32: ...LAARS Heating Systems Page 32 Figure 24 Wiring Diagram Model 1200 Pump Mounted Codes B and E...
Page 53: ...Rheos Boiler and Water Heater Page 53 Figure 42 Electrical Components...
Page 57: ...Rheos Boiler and Water Heater Page 57...
Page 58: ...LAARS Heating Systems Page 58...