Page 44
4.17 Electrical Wiring Connections
This appliance must be electrically grounded. Ensure the electrical receptacle that the combination boiler will
be plugged into, is properly grounded; if wiring directly.
Do not attach the ground wire to either the gas or the water piping as plastic pipe or dielectric unions may
isolate the Combination boiler electrically.
The wiring diagrams contained in this manual are for reference purposes only.
Refer to these diagrams and diagrams from external controls used with this appliance. Read, understand,
and follow all wiring instructions.
Do not disconnect the power supply when the unit is in normal operation. Damage caused by freezing is
not covered under the warranty.
Manual(Rocker) switch maximum allowable current for each circulator is 16 amps at 125VAC.
( Housing : Nylon #66 UL 94V-2 , Rocker : Nylon #66 UL 94V-2, Terminal : Copper Alloy )
Terminal block (External power connector) :
DFT-20A-10P (20 amps at 300VAC)
WARNING
Install wiring and electrically ground boiler in accordance with authority having jurisdiction or, in the
absence of such requirements, follow the National Electrical Code, NFPA 70, and/or CSA C22.1
Electrical Code-Part 1 in Canada.
ELECTRICAL SHOCK HAZARD — For your safety, turn off electrical power supply at service
entrance panel before making any electrical connections to avoid possible electric shock hazard.
Failure to do so can cause severe personal injury or death.
SECTION 4. Installation
Manual
Power
Switch
Thermostat
Connection
External
Input
Main Power
CH/Boiler
Pump
Outdoor
Sensor
0 - 10V
L N G L N G
T T
O / S
0-10V
INPUT
R W
Terminal Block
Summary of Contents for MFTCF140
Page 48: ...LAARS Heating Systems Page 46 4 19 Control Board Electrical Diagram SECTION 4 Installation...
Page 65: ...Mascot FT Floor Standing Combination Boiler Page 63 6 2 Fault Tree Analysis 1 Flame detection...
Page 75: ...Mascot FT Floor Standing Combination Boiler Page 73...
Page 78: ...LAARS Heating Systems Page 76 Heat Exchanger MFTCF140...