SECTION VI:  GAS CONNECTIONS 

 

 

WARNING

 

Connect this water heater only to the type of gas as shown on the rating plate.  Use clean black iron 

pipe or equivalent material approved by local codes and ordinances.  (Dirt and scale from the pipe can 

enter the gas valve and cause it to malfunction).  The inlet gas line must have at least a 3 inch (7.62 cm) 

drip leg (sediment trap) installed as close to the water heater’s gas valve as possible.  A ground joint 

union must be installed in the gas supply line, as close to the water heater as possible, to permit 

servicing of the water heater.  Compounds used on the threaded joints of the gas piping must be 

resistant to the action of liquefied petroleum gases/propane gas.  DO NOT apply pipe dope to the gas 

valve inlet and make certain that no pipe dope has become lodged in the inlet screen of the gas valve.  

Extreme care must be taken to ensure no pipe dope enters the gas valve and to avoid excessive torque 

when tightening the gas supply line to the gas valve.  Excessive torque may result in cracking of the gas 

valve housing.  The suggested maximum torque is 31.5 foot lbs. (4.4 kg-m).  The manufacturer of this 

water heater will not be liable for any damage or injury caused as a result of a cracked gas inlet as a 

result of excessive torque.   
This water heater and its gas connection must be leak tested before placing the water heater in 

operation.  Check for gas leaks with a soap and water solution and a brush or a commercial leak 

detector fluid.   

NEVER USE A MATCH OR OPEN FLAME FOR TESTING! 
The water heater is not intended for operation at higher than 10.5 inches water column, for natural gas, 

13.5 inches water column for L.P. supply gas pressure.  Higher gas supply pressures require 

supplemental reducing service regulation.  Exposure to higher gas supply pressure may cause damage 

to the gas controls, which could result in fire or explosion.  If overpressure has occurred such as through 

improper testing of gas lines or emergency malfunction of the supply system, the gas valve must be 

checked for safe operation.  Make sure that the outside vents on the supply regulators and the safety 

vent valves are protected against blockage.  These are parts of the gas supply system, not the water 

heater.  

 

 

WARNING

 

Conversion of this unit from natural gas to L.P., or L.P. to natural gas CANNOT be done in the field.  If the 

gas supply does not match the type shown on the water heater rating plate, then contact your supplier for 

the proper water heater for the building gas supply.   

 

    

CAUTION

 

The water heater and individual shutoff valve must be disconnected from the gas supply piping system 

during any pressure testing of the system at test pressures in excess of 1⁄2 psi (3.5 kPa).  The water 

heater must be isolated from the gas supply piping system by closing its manual shutoff valve during any 

pressure testing of the gas supply system at test pressures equal to or less than 1⁄2 psi (3.5 kPa).  The 

supply line must be capped when not connected to the water heater. 
If copper supply lines are used, they must be internally tinned and certified for gas service. 

 

The gas supply lines must meet all requirements of the National Fuel Gas Code ANSI Z223.1 (Latest 

Edition), or in Canada CAN/CGA B149.1 Natural Gas Installation Code (Latest Edition) or CAN/CGA 

B149.2 Propane Installation Code (Latest Edition).  The gas supply line may need to be larger for the 

EVERHOT

®

 water heaters than a storage water heater in the case of a replacement installation.  Refer to 

the gas piping capacity tables at the end of Section VI (Gas Connections) and in the codes referenced 

above. 

 

A 3” (7.6 cm) drip leg (sediment trap) is required ahead of the gas inlet connection to the water heater.  

See water heater installation illustration.  Install a manual gas shutoff valve before the gas inlet 

connection to the water heater before connecting to the gas line.  A union should be installed before the 

water heater gas connection for disconnection for servicing.  Refer to the piping diagrams (Fig. 2-5) in 

Section V, “Water Connections”. 

 

 

18

Summary of Contents for Everhot IGE-199R Series

Page 1: ...ier call the fire department Installation and service must be performed by a qualified installer service agency or gas supplier WARNING If the information in these instructions is not followed exactly...

Page 2: ...installed in accordance with local codes In the absence of local codes it must be installed in compliance with the National Fuel Gas Code ANSI Z223 1 Latest Edition or in Canada CAN CGA B149 1 Natural...

Page 3: ...et piping of this water heater It is the responsibility of the installing contractor to see that all controls are correctly installed and are properly operating when the installation is complete DO NO...

Page 4: ...all a qualified service agency to inspect the appliance and to replace any part of the control system including gas controls which has been under water DO NOT attempt to use this water heater with any...

Page 5: ...e maximum flow is based upon a minimum water pressure of 30 PSI Flow Rate Gal Min 7 3 5 9 4 2 3 3 2 8 2 4 IGE 199R 10N IGE 199R 10X IGE 199C 5N 199 000 15 000 First Hour Supply Gal Hr 438 354 252 198...

Page 6: ...ximum input 0 9 Minimum input Venting System Forced Combustion external vent For Outdoor Installation Only Setpoint Temperature Without remote temperature control 140 F Commercial models 120 F Residen...

Page 7: ...kg and can be installed by 1 person The burners ignite within 3 seconds of water flow 1 2 gallon minute 1 9 L m minimum by direct spark ignition There is no standing pilot A variable speed combustion...

Page 8: ...ble Contact your gas supplier or plumbing professional for more information Liquefied petroleum gases propane gas is heavier than air and will remain at floor level if there is a leak Basements crawl...

Page 9: ...eat temperatures are necessary to obtain adequate booster output add an ASSE approved mixing valve for hot water supplied to fixtures UNPACKING INSPECT SHIPMENT carefully for any signs of damage 1 All...

Page 10: ...erhangs windows doors etc Also avoid locations where there is heavy water runoff from roofs Determine the proper height and location for the water heater to be installed Consider the water and gas con...

Page 11: ...3 ppm Up to 0 05 ppm Up to 5 ppm Lime Condition Warning Signal If the EVERHOT water heater is operated under hard water conditions without a water conditioner the error code LC may flash on the remote...

Page 12: ...ris Debris will clog the mesh strainer of the inlet filter The inlet strainer prevents debris from damaging the flow sensor or clogging the coil It may need to be cleaned periodically and should be cl...

Page 13: ...Recommended Piping for a Basic Installation Fig 2 13...

Page 14: ...illustration The drain solenoids are recommended for very cold climates to prevent water heater freeze damage where power failures from ice and windstorms occur The electrical connections for the two...

Page 15: ...Recommended Piping for a Circulation System Fig 4 15...

Page 16: ...Recommended Piping for Back up Storage System For hotels motels and other high flow applications Fig 5 Note The Primary Circulator for the water heating loop must be sized for 21 GPM 35 Ft Head 16...

Page 17: ...stall the pressure relief valve into a tee connection from the hot water outlet of the water heater Note Some models may already be equipped or supplied with an installed pressure relief valve Verify...

Page 18: ...uch as through improper testing of gas lines or emergency malfunction of the supply system the gas valve must be checked for safe operation Make sure that the outside vents on the supply regulators an...

Page 19: ...9 12 15 18 21 24 27 30 38 45 53 61 3 4 278 190 152 130 115 105 96 90 84 79 72 64 59 55 1 520 350 285 245 215 195 180 170 160 150 130 120 110 100 1 1 4 1050 730 590 500 440 400 370 350 320 305 275 250...

Page 20: ...around the plugs 7 Replace the front control panel Restore electrical power to the water heater NOTICE If the gas supply pressure is below the specified value check the gas piping to insure that it is...

Page 21: ...by local code then provide a three wire GFI grounding type receptacle within reach of the control box Provide a grounded line cord and connect to the black and white power supply and green ground scr...

Page 22: ...Wiring Diagram WARNING DO NOT adjust any dipswitch settings on PC board 22...

Page 23: ...Wiring Diagram Schematic 23...

Page 24: ...re for sanitizing purposes Always check water temperature by hand before entering the shower or bath The temperature may have been changed Test the temperature of the water with your hand or elbow bef...

Page 25: ...or the cable using a 1 4 6 4 mm drill bit 3 Run the cable from the control to the water heater or another control which ever is closer or more convenient 4 Remove the face plate from the remote contro...

Page 26: ...e setting is 140 F In addition the control will display fault codes in the event the water heater needs service Up to two additional optional remote controls may be purchased and installed if desired...

Page 27: ...ontrols with the power on to the water heater There are 120 volt terminals and wiring next to the remote control connections inside the unit All servicing and wiring must be performed by a qualified i...

Page 28: ...vice professional 1 Flooding to or above the level of the burner or controls 2 External firing 3 Damage 4 Firing without water 5 Sooting NEVER OPERATE THE WATER HEATER WITHOUT FIRST BEING CERTAIN IT I...

Page 29: ...ely call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department OPERATING INSTRUCTIONS 1 STOP Read the safety i...

Page 30: ...er lines A licensed plumbing professional or local plumbing authority should be consulted CAUTION This water heater when set at a lower temperature setting is not capable of producing hot water of suf...

Page 31: ...o 9 error codes if any stored in memory that has been experienced Any error codes will be displayed on the digital monitor in sequence starting with the most recent code 7 To display the water flow th...

Page 32: ...matically start heating water whenever a hot water faucet is opened The remote temperature control s will indicate hot water use with the green IN USE indicator 5 All controls can also display diagnos...

Page 33: ...any faucet in the system Be careful whenever using hot water to avoid scalding injury Certain appliances such as dishwashers and automatic clothes washers may require increased temperature water By se...

Page 34: ...yed Fault Remedy 10 Air supply or exhaust blockage Check for a restriction in the exhaust vent 11 No Ignition Check to make sure the gas supply is on to the water heater 12 Flame Failure grounding fai...

Page 35: ...Check the front vent outlet for any obstructions 4 All electric motors are permanently lubricated and do not need oiling Remove the combustion air blower and clean wheel and housing with soft brush or...

Page 36: ...ut the lime deposits Use the following procedure and diagram fig 13 to flush the heat exchanger and remove the lime scale 1 Disconnect power to the water heater 2 Close valves in the cold water inlet...

Page 37: ...erate the water heater To remedy this situation either increase the total water flow from the tap or using the remote temperature controller decrease the setpoint temperature of the water heater to th...

Page 38: ...SCHEMATIC DIAGRAM OF INTERNAL PARTS 38...

Page 39: ...SECTION X PARTS LIST Cabinet Note Can purchase additional controls for remote locations 39...

Page 40: ...Internal Components 40...

Page 41: ...Internal Components 41...

Page 42: ...Electrical Components 42...

Page 43: ...ber Front Plate 1 116 Spark Electrode 1 117 Flame Sense Rod 1 118 Electrode Gasket 1 119 Electrode Holder 1 120 Upper Combustion Chamber Gasket 1 122 Fan Casing Assembly 1 123 Blower Motor 1 127 Blowe...

Page 44: ...805 Screw 3 806 Screw 4 807 Washer 4 808 Screw 4 809 Screw 4 810 O Ring 3 813 O Ring 2 814 O Ring 2 815 O Ring 2 817 O Ring 1 818 Gasket 2 238 44959 00 Installation and Operating Instructions 1 239 4...

Reviews: