20
4. Turn power on (after completing electrical connections – refer to Section VII, “Electrical
Connections”) and fully open a hot water tap.
5. Measure the gas pressures to see that these are within the specified limits below:
Supply Pressure:
Nat. Gas: Min.: 6”, Max.: 10.5” w.c.
L.P. Gas: Min.: 10”, Max.: 13.5” w.c.
Manifold Pressure:
Nat. Gas: 3.4” w.c. High Fire, 0.6” w.c. Low Fire
L.P. Gas: 5.1” w.c. High Fire, 0.9” w.c. Low Fire
6. Turn off the hot water faucets. Disconnect the electrical power to the water heater. Remove the
pressure gauges and replace the plugs. Check for gas leaks around the plugs.
7. Replace the front control panel. Restore electrical power to the water heater.
NOTICE
If the gas supply pressure is below the specified value, check the gas piping to insure that it is the correct
size for all the gas appliances on line. Check the supply pressure with all the gas appliances in operation.
The manifold pressure will vary with the water flow rate. Several hot water faucets may need to be
opened with the temperature control set on the highest setting in order to get maximum high fire manifold
pressure. If the manifold pressure is below the specified value and there is sufficient water pressure and
flow, be sure the inlet gas pressure is within the specified limits before attempting to adjust the manifold
pressure.
Summary of Contents for Everhot IGE-199R Series
Page 13: ...Recommended Piping for a Basic Installation Fig 2 13...
Page 15: ...Recommended Piping for a Circulation System Fig 4 15...
Page 22: ...Wiring Diagram WARNING DO NOT adjust any dipswitch settings on PC board 22...
Page 23: ...Wiring Diagram Schematic 23...
Page 38: ...SCHEMATIC DIAGRAM OF INTERNAL PARTS 38...
Page 39: ...SECTION X PARTS LIST Cabinet Note Can purchase additional controls for remote locations 39...
Page 40: ...Internal Components 40...
Page 41: ...Internal Components 41...
Page 42: ...Electrical Components 42...