background image

9600 HWG Water Heater

Page 7

Cold water supply piping, fittings and accessories.

1.

Install a strainer between the 9600 HWG and the

system. For proper pipe size and distance

limitations, refer to Table 3.

2.

Connect a drain valve and a shut off valve to the

9600 HWG cold inlet. On multiple units install a

check valve at each unit’s cold water inlet.

3.

Where check valves have been installed on cold

water inlet piping, check to be sure system has

an adequately sized expansion tank to allow

thermal expansion to occur.

Hot water supply piping.

Follow the manufacturer’s guidelines for

completion of the hot water system connections.

NOTE: A listed temperature and pressure

relief valve listed as complying with the Standard

for Relief Valves and Automatic Gas Shutoff

Devices for Hot Water Supply Systems, 1). ANSI

Z21.22 latest edition, or 2). CAN / CGA 1 - 4.4, of

suitable discharge capacity must be installed in the

separate storage tank system.

3.4 Tank Temperature Control

The 9600 HWG is turned on and off by a remote

tank aquastat. Locate the aquastat above the cold

water inlet fitting in the separate storage tank. The

9600 HWG draws water off the bottom of the tank

and pumps hot water back into the tank. When the hot

water level reaches the level of the aquastat, the

aquastat switch will open and turn off the 9600 HWG.

Please contact your factory representative if you

have any questions about storage tank application.

If a water heater is installed in a closed water

supply system, such as one having a backflow

preventer in a cold water supply line, means shall be

provided to control thermal expansion, such as a

properly sized potable water expansion tank.

If the relief valve on the appliance discharges

periodically, this may be due to thermal expansion in

Table 3. Water pipe and tube sizing between unit and tank.

Note:

 This unit must be installed in a pressurized closed

system that maintains a minimum of 10 psi static pressure.

If water hardness is greater than 10 grains, a water soft-

ening or particle suspension device must

 be installed be-

fore the heater, or warranty will be void.

Copper tube or

pipe size

Maximum

allowable tubing

length

Amount

deducted for

each additional

90° elbow

Amount

deducted for

each additional

45° elbow

1¼"

40'

2'

1½'

1½"

120'

2'

1½'

2"

270'

2'

1½'

a closed water supply system. Contact the water

supplier or local plumbing inspector on how to correct

this situation. Do not plug the relief valve.

No valves shall be placed between the tank T &

P relief valve and the tank. Pipe the outlet from the

relief valve such that any discharge from the relief

valve will be conducted to a suitable place for

disposal when relief occurs. Do not reduce line size or

install any valves in this line. The line must be

installed to allow complete drainage of both the valve

and the line.

3.5 Condensate Drain Connection

A black plastic fitting (labeled CONDENSATE)

is located on the side of the cabinet. This fitting will

accept 1/2" OD plastic tubing.
1.

Connect a plastic tube between the fitting and

the floor drain or condensate pump if a floor

drain is not accessible.

NOTE:

 Connecting tubing must run

DOWNWARDS from the level of the fitting. See

Figure 8.

2.

Above the fitting is a hole in the cabinet. Behind

this hole is a 1/2" OD tube which serves as a

condensate relief if the lower drain becomes

blocked (see Figure 9).

3.

Run this condensate relief tube through the hole

in cabinet and to a drain pan. DO NOT pipe in

common with condensate drain fitted in A

above.

3.6 Electrical Connections

All electrical wiring must conform to local codes

and/or the 1). National Electrical Code ANSI/NFPA

No. 70-Latest Edition, or 2). The CSA Standard C22.1

“Canadian Electrical Code - Part 1”.

Single pole switches, including those of safety

controls and protective devices must not be wired in a

grounded line.

All electrical connections are made in the field

wiring box which is located on the left side of the

unit.

Figure 5. Gas supply piping.

To

9600 HWG

Manual Main

Shut Off

Gas Supply

Drip Leg

Cap

Summary of Contents for 9600 HWG

Page 1: ...service technician qualified in hot water boiler installation and maintenance Improper installation and or operation could create carbon monoxide gas in flue gases which could cause serious injury pro...

Page 2: ...ide Wall 5 2 4 Locating Unit for Proper Vent Height 5 2 5 Locating Unit with Respect to Ventilation 5 2 6 Locating Unit with Respect to Storage Tanks 5 SECTION 3 Installation 3 1 Installing Vent Pipin...

Page 3: ...rements take precedence over the general instructions contained herein All electrical wiring is to be done in accordance with local codes or in the absence of local codes with 1 the National Electrica...

Page 4: ...y AGA CGA for installation on combustible flooring in basements in closets utility rooms or alcoves It must not be installed on carpeting The location for the unit should be chosen with regard to the...

Page 5: ...vent locations you select must permit direct pipe runs to the terminal from the boiler Since the 9600 HWG Water Heater is designed to drain any water that collects in the vent it is important that yo...

Page 6: ...Install a shut off valve in the piping between the thermometer fitting and the tank The following steps are recommended for vent installation 1 Obtain the necessary 3 or 4 diameter plastic piping and...

Page 7: ...ntains a minimum of 10 psi static pressure If water hardness is greater than 10 grains a water soft ening or particle suspension device must be installed be fore the heater or warranty will be void Co...

Page 8: ...Page 8 LAARS Heating Systems Figure 7 Two temperature system Figure 6 Single 9600 HWG Storage Tank...

Page 9: ...9600 HWG Water Heater Page 9 Figure 8 Multiple 9600 HWG s storage tanks...

Page 10: ...t attempt because of air contained in gas lines In this case blower will stop after 5 minutes Should this happen turn off main switch Wait five minutes and turn on switch again If burner fails three t...

Page 11: ...s or hose see Figure 9 3 The pressure relief valve should be operated manually at least once a year To do this place a suitable container under the relief valve drain pipe The discharge from this valv...

Page 12: ...tall new O ring valve top and replace valve top on valve and install and tighten screws 6 Restore pressure to water heater bleed air from the petcock on the valve and restart water heater 7 Replace ac...

Page 13: ...heater for the space heating application shall be suitable for use with potable water Toxic chemicals such as used for boiler treatment shall not be introduced into the potable water used for space h...

Page 14: ...Defective low limit operating control safety limit or system differential pressure switch 2 Jump control wires one control at a time to identify open circuit in control no continuity FOR DIAGNOSIS ONL...

Page 15: ...ge 15 Figure 16 Wiring diagram Caution Label all wires prior to disconnection when servicing controls Wiring errors can cause improper and dangerous operation Verify Proper Operation After Servicing F...

Page 16: ...Page 16 LAARS Heating Systems Figure 18 Lighting and shutdown procedures...

Page 17: ...nstallation manual Set regulator for maximum run pressure of 9 3 Remove blower and inspect flame holder burner for hole 4 Check that the blower flanges and gas piping are sealed 6 4 Occasional Lockout...

Page 18: ...310 Blower Assembly HWG 250 2400 086 Combustion Coil Assembly 9 2400 082 Flame Holder 7 2400 308 Flame Holder HWG 250 2400 286 Ignitor 2400 088 Capacitor Motor Starter 2400 224 Control Board 2400 014...

Page 19: ...9600 HWG Water Heater Page 19...

Page 20: ...vice Advisors 20 Industrial Way Rochester NH 03867 603 335 6300 Fax 603 335 3355 Applications Engineering 1869 Sismet Road Mississauga Ontario Canada L4W 1W8 905 238 0100 Fax 905 366 0130 www Laars co...

Reviews: