Electrical Specifications
Important:
Qualified and licensed electricians must perform all electrical hookups.
The following specifications must be followed in order to ensure proper performance
and safety.
WARNING:
Starting an incorrectly wired
spa / hot tub
could cause
severe damage to the mechanical equipment or even
bodily harm. Have your licensed electrician verify GFCI
wiring with the schematics on pages 17 - 18 prior to
starting the
spa
/ hot tub or call your local dealer.
CAUTION:
Failure to abide by specifications listed may result in
damage to the equipment and will void the warranty.
All spa / hot tubs must be wired with a 50 Ampere (A) breaker (or according to IEE wire
regulations for export models). Failure to do so will cause equipment damage and will
not be covered under your guarantee.
All spa / hot tubs must be protected with an over current protective device with built-in
GFCI in the service panel.
Volts
(V)
Freq.
(Hz)
Phase
Rating
(A)
GFCI
(A)
Wire size from GFCI
to Main Panel*
# of
Terminals
on plug
240 60 1 40 50
6-3 plus ground (up to 130’)
4-3 plus ground (up to 230’)
2-3 plus ground (up to 360’)
4
Table 2 – Wire Size Chart
CAUTION:
Test the GFCI before each use of the spa / hot tub.
* Use only solid copper wire.