30
english
If you wish to modify the parameter, use the
K1gR1
(+) or
K2gR1
(-) keys.
Once the setting has been made, press the
K5gR1
key (MENU) to switch to a display of the parameters for
PID type thermostating:
The display shows
kP kI kD
xx.x y.yy zz.z
where xx.x is the proportional correction constant
where y.yy is the integrated correction constant
where zz.z is the derivative correction constant
each value is selectable between 0.1÷99.9°C in steps of 0.1.
The setting is PID by default with the following parameters:
The display shows
kP kI kD
08.0 0.15 10.0
whereas to enable adjustment with hysteresis of 2°C, all the k values need to be 0
The display shows
kP kI kD
00.0 0.00 00.0
If you wish to modify the parameter, use the
K1gR1
(+) or
K2gR1
(-) keys.
Once the setting has been made, press the
K5gR1
key (MENU) to switch to a display of the setting of the
adjustment range of the PID with respect to the setpoint temperature.
Outside this range, the adjustment is always on/off.
The display shows
PID adjustment
x°C
where x is the value in degrees of the range and it is a selectable value between 2÷5°C in steps of 1°C
If you wish to modify the parameter, use the
K1gR1
(+) or
K2gR1
(-) keys.
Once the setting has been made, press the
K5gR1
key (MENU) to switch to a display of the setting of the
boiler water level filling time-out:
The display shows
Filling Up T-Out
xxx
Selectable value: between 10 ÷ 250' in steps of 1 minute
If you wish to modify the parameter, use the
K1gR1
(+) or
K2gR1
(-) keys.
Once the time-out has been programmed, to move on to the next menu press K5GR1 (MENU); this will take
you to the water softener filter litre setting