Mounting
When mounting the LMESpro, the location chosen for the charger should be within an ambient temperature range
of -40
to 122˚F (
-40 to 50
˚C) with a non
-condensing relative humidity no higher than 95%. The LMESpro should
be mounted in an area free of flammable & explosive materials and away from drips, splatter, or moving parts.
To be mounted on a non-combustible surface. The LMESpro utilizes convection cooling with a heat-sink facing
the mounting surface; mount in an upright position as shown in Figure 1 to promote convection air flow. Provide
clearance for at least 6in (152mm) of free air must be maintained on the left/right sides, and at least 6
”
(152mm)
top/bottom sides for cooling. Maintain 36in (914mm) or more of clearance at the front of the charger in order to
allow for operation and maintenance. Install the LMESpro using appropriate hardware on the wall. When using
multiple adjacent LMESpro chargers, do not mount them 1 above the other, mount them side-by-side with a
minimum
of 6” between them. Avoid mounting the
LMESpro directly over another heat source.
Figure 1
–
LMESpro Mounting Dimensions
Figure 2 - Distance to obstruction of free air flow