19
4.18 Battery Mode Backup Timer Display Setting (Set 18)
The 18 Setting allows the user to select the value to display when the Battery
Mode Backup Timer is engaged. Below are the available selections to display:
•
EAT:
When the Battery Mode Backup Timer is engaged, the display will
show
the remaining backup time (Default)
•
RAT:
When the Battery Mode Backup Timer is engaged, the display will show
the accumulated backup
time so far.
4.19 AC Mains Voltage Range (Set 19)
The 07 Setting allows the user to adjust the HLS (High Loss Setting) and the LLS
(Low Loss Setting) for the incoming AC mains supply. The HLS is the maximum
allowable mains supply voltage threshold. The LLS is the minimum allowable
mains supply voltage threshold. If any of the thresholds are surpassed, the UPS
will not utilize the AC mains supply (Online Mode/Bypass Mode) and will enter
Battery Mode (if applicable).
Use the Up/Down buttons to select HLS or LLS and confirm selection using the OFF/ENTER button. Below are the
adjustment ranges for the Loss Settings:
•
100-127VAC Models:
o
LLS: 50VAC to 85VAC (Default: 85V)
o
HLS: 140VAC to 150VAC (Default: 132V)
•
200-240VAC Models:
o
LLS: 170VAC to 220VAC (Default: 170V)
o
HLS: 230VAC to 264VAC (Default: 264V)
4.20 Escape (Set 00)
The 00 Setting allows the user to exit the Settings Menu and return to the main
screen. Press the OFF/ENTER to exit the menu.
Faults Reference Code
Fault Event
Fault Code
Icon
Fault Event
Fault Code
Icon
Bus Start Fail
01
x
High Battery Voltage
27
x
Bus Over
02
x
Low Battery Voltage
28
x
Bus Under
03
x
Charger Output Shorted
2A
x
Inverter Soft Start Fail
11
x
Over Temperature
41
x
Inverter Voltage High
12
x
Overload
43
Inverter Voltage Low
13
x
Charger Failure
45
x
Inverter Output Shorted
14
x
Over Input Current
49
x