background image

INSTRUCTION / TROUBLESHOOTING MANUAL FOR MODEL A75M  

PAGE 9 OF 13 

A75M TROUBLESHOOTING 

 

INSTRUCTIONS

 

 

Before troubleshooting unit, check for shipping damage. (i.e. broken wires, loose connections, etc.) 

 

Quick-Check A75M Trouble Analysis

 

 

Problem:  Blown AC input fuse.

 

1.

 

Check AC input voltage with tap setting on power transformer and control transformer.  If AC input 

and tap setting agree, see step #2. 

2.

 

Check AC input current draw after replacing blown AC fuse.  NOTE:  If AC fuse clears as soon as 

the  AC  contactor  pulls  in,  go  to  STEP  #5.    On  three  (3)  phase  units,  if  the  AC  current  is  not 

approximately equal, check the AC voltage input to the S2A-123 printed circuit board.  Connector 

#1, 4-5, 5-6, 6-4 should be 100 Vac. - 220 Vac.  If this voltage is not there, retrace the wiring back 

to the SCR/Diode modules.  If voltage is there, continue to step #3. 

3.

 

Check the AC voltage output on the S2A-123 printed circuit board, Connector #2, 4-1, 4-2, 4-3.  

Voltages must be approximately equal and greater than 5 Vac.  If it is not greater than 5 Vac., 

replace the S2A-123 printed circuit board. 

4.

 

Connect charger to discharged battery, check output voltage and voltage across charger shunt bar.  

If output voltage is below 2.3 Vpc., the voltage across shunt must not exceed 135mV.  If it is over 

135mV, adjust pots on the S2A-320 printed circuit board counterclockwise which lowers the output 

until 97mV across the shunt bar is indicated. 

S2A-320 POT ADJUSTMENTS 

P3  LOW START RATE* 
P4  MID START RATE 
P6  HIGH START RATE 
P8  LOW FINISH RATE 
P9  MID FINISH RATE 

P10  HIGH FINISH RATE 
P11  START/FINISH THRESHOLD VOLTAGE 

P1  HIGH VOLTAGE CLAMP 

 

Verify  the  jumper  selection  on  the  AC  input  terminal 
block.  If Low Start Rating is 101A and 250A/`100mV 
shunt  is  used,  Adjust  P3  until  101A  100mV/250A  = 
40.4mV across the shunt bar is indicated. 

5.

 

If AC input fuse clears when the AC contactor pulls in make sure the correct AC fuses are being 

used, time delay fuses.  If the correct AC fuses are being used, disconnect P1 connector from the 

FC6 printed circuit board. 

6.

 

Replace blown AC fuse, turn on AC power.  (If fuse is good, defective S2A-320 or FC6 p.c. board.) 

If fuse still clears, problem is a shorted SCR/Diode module or power transformer. 

7.

 

Separate secondary leads from P.T. to SCR/Diode modules.  If fuse still clears, problem is in the 

(P.T.) power transformer.  If fuse is good, problem could be in the SCR/Diode module. 

SEE SCR/DIODE TROUBLESHOOTING GUIDE. 

Summary of Contents for A75M

Page 1: ...L A75M MINING BATTERY CHARGER Digital Volt Amp Meter and Electronic Timer ECN DATE CPN112410 17268 10 06 17589 9 07 17076 2 06 106 BRADROCK DRIVE DES PLAINES IL 60018 1967 847 299 1188 FAX 847 299 306...

Page 2: ...low a spark or flame in vicinity of a battery f Be extra cautious DO NOT drop metal onto a battery It might spark or short circuit the battery or cause an explosion g Remove personal metal items such...

Page 3: ...the claim to La Marche Mfg may void warranty service for any physical damages reported for repair HANDLING WARNING Equipment can be very heavy and top heavy Use adequate manpower or equipment for hand...

Page 4: ...Charged Battery Automatic 12 hour override timer 3 Hour timing after 80 normal mode 6 Hour timing after 80 equalize mode 3 Selectable current ratings Digital Display Indicates amps volts amp hours ela...

Page 5: ...sensing is being disabled and the wrong battery could be being connected An On Off switch allows you to turn off the charger when disconnecting the battery during the charge cycle The on off switch m...

Page 6: ...unit will not start and the digital display will indicate number 0003 The charger will automatically turn off at the end of the charge cycle An on off switch is provided to de energize the charger Be...

Page 7: ...is connected to the positive battery terminal and the negative terminal is connected to the negative of the battery A grounding connection is also provided for complete protection Once properly instal...

Page 8: ...tween the AMP HOURS CHARGE TIME and COOLING TIME The COOLING TIME is the time since the charge cycle completed and is indicated in hours and minutes When showing the CHARGE TIME the AMP HOURS light wi...

Page 9: ...check output voltage and voltage across charger shunt bar If output voltage is below 2 3 Vpc the voltage across shunt must not exceed 135mV If it is over 135mV adjust pots on the S2A 320 printed circ...

Page 10: ...ective S2A 320 Drive Board 2 Shorted MOV Metal Oxide Varistor NOTE Voltage across secondary of control transformer X1 X2 120Vac Problem Complete ON but battery not charged 1 Record all readings on dig...

Page 11: ...DULES A75M 3 PHASE 1 Disconnect power transformer secondary wire from top connection of module 2 Disconnect positive bus bar from module 3 Disconnect negative bus bar from module 4 Disconnect 6 wires...

Page 12: ...t panel meters and alarms for accuracy 4th Year REPEAT ABOVE WITH THE ADDITION OF 1 Check relay contacts for pitting or corrosion 2 Check capacitors for leakage 7th Year REPEAT ALL WITH THE ADDITION O...

Page 13: ...purchaser elects not to return the equipment to the factory and wishes a factory service representative to make adjustments and or repairs at the equipment location La Marche s field service labor rat...

Reviews: