1. Open louvered access panel opposite burner end of

heater.  Disconnect motor leads.

2. Remove screws securing motor mounting plate to

housing.

3. Pull fan and motor assembly from housing.

4. Loosen set screws on fan wheel.

5. Pull fan wheel from motor shaft.

6. Remove the four nuts securing motor to mounting

plate.

FIG. 16

MOTOR MOUNT PLATE

FAN WHEEL

MOTOR

CLEARANCE

PREMIER  80     3/16 IN/4.7 mm
PREMIER 170    1/8 IN./3.2mm

MOTOR AND FAN WHEEL

1. Close the fuel supply valve to the heater and

disconnect the electrical supply before servicing

unless necessary for your service procedure.

2. Clean the heater’s orifice with compressed air or a

soft, dry rag.  Do not use files, drills, broaches, etc. to

clean the orifice hole.  Doing so will enlarge the hole,

causing combustion or ignition problems.  Replace

the orifice if it cannot be cleaned properly.

3. The high limit switches, HEAT/VENT switch, and

thermostat can be tested by disconnecting the leads

at the component, and jumpering the leads together:

-- Reconnect the electrical supply and open fuel supply

valves.

-- If the heater lights, the component is defective and

must be replaced.

-- Do not leave the jumper on or operate the heater if

the part is defective.  Replace the part immediately.

-- An alternate method for checking the components is

to perform a continuity check.

4. The air proving switch must not be jumpered. If

jumpered, the ignition control will not allow heater

operation.  Test the air proving switch for continuity.  If

defective, replace the switch.

5. Open the respective case panel for access to burner

or fan related components.

6. Disconnect the electrical leads for the respective

component.

7. For reassembly, reverse the respective service

procedure.  Ensure gas connections are tightened

securely.

8. After servicing, start the heater to ensure proper

operation and check for gas leaks.

WARNING

Burn Hazard

Heater surfaces are hot for a period of time after the

heater has been shut down.

Allow the heater to cool before performing service,

maintenance, or cleaning.

Failure to follow this warning will result in burns

causing injury.

WARNING

Fire and Explosion Hazard

Do not disassemble or attempt to repair any heater

components or gas train components.

All component parts must be replaced if defects are

found.

Failure to follow this warning will result in fire or

explosions, causing property damage, injury, or death.

GENERAL

Summary of Contents for Premier TS080

Page 1: ...TTENTION ALL USERS This heater has been tested and evaluated by C S A International in accordance with the requirements of Standard ANSI Z83 7l CSA 2 14 and is listed and approved as a ductable direct...

Page 2: ......

Page 3: ...erty damage personal injury or loss of life GENERAL HAZARD WARNING Failure to comply with the precautions and instructions provided with this heater can result in Death Serious bodily injury or burns...

Page 4: ...mier 80 30 31 Premier 170 32 33 Warranty Policy 34 Replacement Parts and Service 34 Table of Contents General Information This Owner s Manual includes all options and accessories commonly used on this...

Page 5: ...75 x 34 x 51 30 75x18 25 x 28 25 78 x 46 3 x 71 7 TOP 1 0 3 SIDES 1 0 3 BACK 1 0 3 BLOWER OUTLET GAS Propane Gas U S 6 1 83 Canada 3 05 SUPPLY Natural Gas N A Net Weight lbs kg 81 36 7 153 69 4 Shipp...

Page 6: ...If there is an underground leak the movement of gas through the soil can filter the odorant Propane gas odor may differ in intensity at different levels Since propane gas is heavier than air there may...

Page 7: ...r is equipped with manual reset high limit switches an air proving switch and a redundant gas control valve Never operate the heater with any safety device that has been bypassed Do not operate this h...

Page 8: ...eading of the heated air inside the tent End Diffuser Part Number 26350 DO NOT USE ANY OTHER DUCTWORK DUCTING FIELD FABRICATED DUCTS TARPS STOVE PIPE or any other means of making the connection betwee...

Page 9: ...opane gas vapor withdrawal only Do not use the heater in an propane gas liquid withdrawal system or application If you are in doubt contact the L B White Co Inc 14 The heater must be installed so as n...

Page 10: ...e hanger to cage nuts on back of heater b Mount the hanger using the 1 4 20 x 3 4 in bolts and 1 4 in flat washers Tighten securely See Fig 2 2 Thermostat Storage Bracket Assembly a Align regulator st...

Page 11: ...WITH81 2 LEGS ANDAXLEHOLE 1BOLT5 16 18X1 AND1WASHER5 16 ATEACHEND BOLTS5 16 18X1 QUANTITY10 COTTER PIN See Fig 4 for assembly of components Ensure all hardware is tightened securely WHEEL LEG LIFTING...

Page 12: ...t FIG 8 THERMOSTAT ASSEMBLY RIGIDEND SWIVELEND ADAPTER REGULATORIN BRACKET POWERCORD HEAVYDUTY EXTENSIONCORD WITHGROUND SERIESTAPPLUG THERMOSTAT 1 Connect rigid end of hose to regulator outlet Connect...

Page 13: ...Position duct as shown Eliminate any kinks in duct FIG 9 3 04 m CAGENUTS SLOT WINGSCREW INSERTTABATBOTTOM OFDIFFUSERINTOSLOT BEFORETIGHTENINGWING SCREWSINTOCAGENUTS 1 See Fig 10 for installation of u...

Page 14: ...rotected from damage and water entry Natural Gas Heaters A regulator is required if the supply pressure to the heater is above the maximum pressure stated on the heater s dataplate Connect the natural...

Page 15: ...gnition before air is finally purged from line and ignition takes place FIG 15 When the switch is set to heat four status lights see Fig 15 will be activated in sequence as specific circuits are check...

Page 16: ...ir or a soft brush or dry rag on its case and internal components At this time dust off the motor case to prevent the motor from over heating b At least once a year give the heater a thorough cleaning...

Page 17: ...s defective and must be replaced Do not leave the jumper on or operate the heater if the part is defective Replace the part immediately An alternate method for checking the components is to perform a...

Page 18: ...cracks are found 17 1 2 IN DISTANCE FROM IGNITER TOPTO BURNERTOP MOUNTING BRACKET IGNITER BRACKET MOUNTING SCREWS IGNITER SENSOR MOUNTING SCREWS HIGHVOLTAGE IGNITION LEAD ELECTRODE GAP IS 1 8 CENTERE...

Page 19: ...Holding the switch by one of its mounting legs apply a small flame only to the sensing portion on the back of the switch Be careful not to melt the plastic housing of the switch when conducting this t...

Page 20: ...ded FIG 24 5 When assembling the control valve to manifold the valve must be offset 8 degrees from the orifice holder to ensure the control valve aligns to its mounting holes See Fig 25 FIG 25 8 ORIFI...

Page 21: ...nd outlet pressure gauges agree with that specified on the dataplate If so then no further checking or adjustment is required Proceed to section D 3 If the inlet pressures do not agree with that speci...

Page 22: ...procedures of the component once the problem is identified by the flow chart DIRECT IGNITION OPERATION SEQUENCE The thermostat calls for heat Light acitvated indicating heater is receiving its main po...

Page 23: ...defective Check continuity Replace power cord Transformer status light is not on Is transformer delivering 24 volts to terminal W on ignition control No Is transformer receiving main voltage Check wi...

Page 24: ...ce fan motor No Yes Are 24 volts received at the air proving switch from terminal PS1 on controller when motor starts Yes Are wires and electrical connections good No Repair or replace wires or connec...

Page 25: ...r end delivering 24 volts to gas control No Is gas control valve receiving 24 volts No Yes Yes Yes Is light receiving 24 volts No Defective wire or terminal connection Repair or replace as needed Yes...

Page 26: ...ntrol is sending high voltage Remove ignition lead from control Hold a screwdriver tip about 1 8 to 3 16 in from male ignition terminal on control Turn heater on Spark should be seen If none replace i...

Page 27: ...proper voltage is not present No No Yes Is proper voltage supplied to selector switch from power cord No Is fan binding on housing Check for damage to fan and housing Repair or replace as necessary Ye...

Page 28: ...K DSI SS T PC HL HL GV APS IGC TX M COMM C W TRANSFORMER PS2 AIRPROVE PS1 AIRPROVE MV VALVE IND MOTOR L1 115 VAC G G G BR BK 115 VAC L1 GY OR OU O BK COMM C TRANSFORMER W AIRPROVE PS1 AIRPROVE PS2 VAL...

Page 29: ...ce that provides an area where burner flame mixes with combustion air thereby providing heat High Limit Switch Safety device wired into the control system which is used to break an electrical circuit...

Page 30: ...29 PREMIER 80 PARTS SCHEMATIC Parts Identification 18 47 13 45 46 44 43 42 41 40 39 38 37 36 35 33 32 31 30 29 27 28 26 25 24 22 23 20 21 19 17 16 15 14 12 11 10 9 7 6 5 4 3 2 1 8 34...

Page 31: ...6378 18 Harness Wire Motor End 26382 19 Base 26380 20 Bracket Igniter Sensor 571663 21 Igniter 571662 22 Burner 26484 23 Screws and Spacers 571211 24 Switch High Limit Burner End 275 F 503933 25 Chamb...

Page 32: ...20 31 PREMIER 170 PART SCHEMATIC 36 17 16 10A 10A 10A 51 49 48 47 46 45 44 43 42 41 39 38 37 35 34 33 32 31 30 29 27 26 25 24 23 21 20 19 15 14 13 12 11 10 9 8 7 5 6 4 3 2 1 50 28 22 18 52 40...

Page 33: ...26441 19 Bracket Ignition Control 26410 20 Ignition Control 25865 21 Orifice Propane Gas 21573 Natural Gas 571624 22 Wire Igniter 25840 23 Igniter 25841 24 Bracket Igniter 25843 25 Burner with Mounti...

Page 34: ...material and workmanship for 24 months from the date of purchase by the end user Warranty is automatic if a component is found defective within 24 months of the date code marked on the part If the de...

Reviews: