CONTROL END MUST BE
1 TO 5 DOWN FROM
HORIZONTAL
THIS
NOT THIS
CONTROL END
OF HEATER
THIS
NOT THIS
HANGING
BRACKET
CONTROL END MUST BE
1 TO 5 DOWN FROM
HORIZONTAL
CONTROL END
OF HEATER
10. It is extremely important to use the proper gas supply
line to assure proper functioning of the heaters.
Typically, 3/4 in. ID black iron pipe is used to supply
gas to the inlet of the zone control panel with 1/2 in.
ID black iron pipe used to convey the gas to the
heaters. However, always consult your fuel gas
supplier, or the L. B. White Co., Inc. for proper line
sizing and installation.
11. Infraconic heaters require a regulated gas supply to
the gas inlet of the product. Exceeding the gas inlet
pressure rating can result in poor performance and
unreliable operation. Refer to page 4 of this manual
for information on gas pressures relating to specific
models.
12. The heater is designed for either L.P. vapor with-
drawal or natural gas, depending on model number.
Do not use this heater in an LPG liquid withdrawal
system. Do not permit LPG in liquid form to enter the
heater at any time.
13. The corrosive atmosphere present in animal
confinement buildings can cause component failure
or heater malfunction. The heater should be
periodically inspected and cleaned in accordance
with the Maintenance and Cleaning Instructions in
this manual. Make sure that livestock is protected by
a back up alarm system that limits high and low
temperatures and also activates appropriate alarms.
14. Take time to understand how to operate and
maintain the heater using the owner’s manual. Make
sure you know how to shut off the gas supply to the
building and to the individual heaters. Contact your
gas supplier if you have any questions.
15. Any defects found in performing any of the service
procedures must be eliminated and defective parts
replaced immediately. Retest the heater before
placing it back into service.
8
INSTALLATION LAYOUT
FOR SAFE CLEARANCES
I17 & I34 - 3 FT. MINIMUM
BROODER TOP TO CEILING
POSITION THE GAS HOSE AND ELECTRICAL POWER CORD
OUTSIDE OF THE HOT ZONE DIRECTLY ABOVE THE HEATER.
POSITION THE GAS HOSE AND POWER CORD TO AVOID
ANY OPPORTUNITY FOR CONTACT WITH THE HOT CANOPY
SURFACE OF THE HEATER.
MINIMUM 3 FT. CLEARANCE
TO COMBUSTIBLES
FLOOR
I17 - 3.5 FT. MINIMUM
I34 - 4.5 FT. MINIMUM
POINT OF COMBUSTION
CONE TO FLOOR
HANG THE HEATER WITH THE
CONTROL END 1 TO 5 DEGREES DOWN
FROM HORIZONTAL (SEE BELOW)
CONTROL PANEL
GAS PIPING
FIG. 2
AATTTTEEN
NTTIIO
ON
N
■
Model I17 heaters utilize an
integral chain hanging bracket
located on the heater’s venturi
tube. Model I34 heaters use
chain hanging clips.
■
Regardless of hanging system,
the installer must make sure
that the heater is installed so
control end of heater is
positioned 1º to 5º down from
horizontal after gas supply hose
is attached.
■
Repositioning of factory
installed key ring into hanging
bracket (for I17) or adjustment
of chain for I34 may be
required.
■
Refer to following illustrations.
M
MO
OD
DEELL II1
17
7
M
MO
OD
DEELL II3
34
4