5.5 List of Display Message
Low battery warning
Temperature monitor for internal resistance, available at Loop,
PSC/PFC & RCD function. Further measurements are
suspended until the “
” symbol disappears.
Measuring
Measurements in progress
Live Circuit
Live circuit warning
(Continuity / Insulation Function)
PE Hi V
Caution : Presence of 100V or more at PE terminal, appears
when touching the Touch Pad
L-N >20Ω
Alert : Presence of 20Ω or more between Line - Neutral at ATT
measurement
Noise
Caution : Presence of noise in the circuit under test during ATT
measurement. ATT function should be disabled to continue
measurements.
N - PE Hi V
Caution: Presence of high voltage between NEUTRAL - EARTH
during ATT measurement. ATT function should be disabled to
continue measurements.
Uc > UL
Caution : Uc at RCD measurement is exceeding the preset UL
value (25 or 50V).
no
Error message : When on the RCD function, RCD tripped before
measuring RCD trip time. Selected IΔn value may not be correct.
When on the LOOP, PSC/PFC function, supply may have been
interrupted.
Wiring check for LOOP, PSC/PFC function
OK
Appears when all results passed during the RCD Auto Test
function.
×
NO
Appears when any results failed during the RCD Auto Test
function.
R
H
Hi, Rs Hi
Appears when a Probe resistance of H terminal (R
H
) or of S terminal (R
S
)
at Earth measurement is exceeded the measurable range.
No 3-phase system
Appears to indicate wrong connection at Phase Rotation check.