![Kyoritsu Electrical Instruments Works KEW 4506 Instruction Manual Download Page 33](http://html.mh-extra.com/html/kyoritsu-electrical-instruments-works/kew-4506/kew-4506_instruction-manual_2017199033.webp)
̶ 31 ̶
(2) Press
button to select “2P”.
Note
● Settings always restore to the ones for 3P socket whenever
powering on the tester.
● If the earth terminal of the outlet to be tested is earthed at 2P
test, the settings automatically change to the ones for “3P”.
(3) Connection
#
CAUTION
● When earth pole (E) is connected, settings automatically
change to the ones for “3P”.
● Kyoritsu is by no means liable for any damage or injury resulting
from the use of 3P/ 2P conversion adapter.
A 3P/ 2P conversion adapter, which is required to connect with
2P outlet, isn’t supplied with the tester. Prepare commercially
available 3P/ 2P conversion adapter to connect the tester to 2P
outlet, and attach it to the plug part of test lead with IEC connector
KAMP10 or MODEL 7284 before conducting a test. Observe the
correct orientation and connect to the outlet to be tested.
Note
● When conducting a test, stand on the floor and do not touch
anything other than the tester to measure electrical potentials
precisely.
● If 3P/ 2P conversion adapter you prepared has exposed metal
terminals, do not touch the metal terminals during a test. KEW
4506 judges as “N-E Reverse” even if the outlet under test is
correctly wired.