̶ 28 ̶
When KEW 4506 detects miswiring, any of the following indications
is displayed on the LCD. See Fig. 6-20. In addition, red LED
indicator lights up, as Fig. 6-21 shows, with continuous beep
sounds.
Fig. 6-20
L-N Reverse
L-E Reverse
N-E Reverse
Abnormal voltage N Non-connect E Non-connect N-E unjudgeable
Fig.
6-21
Red LED lights up.
● Measured value displayed on the bottom area of LCD in case of
“N-E Reverse”
Resistance value : N-E resistance determined by measuring
resistance between neutral wire (N) and
earth wire (E) is displayed.
Voltage value
: N-E voltage is displayed if voltage between
N-E is 8 V or higher. When N-E voltage is
higher than 8 V, KEW 4506 cannot measure
resistance.
Summary of Contents for KEW 4506