Kyland Technology (Shanghai) Co., Ltd PTS-DR200 Time Server
- 33 -
[Figure 3-20] Output Setting Screen (O3)
Table 19 – Output Setting (O3)
Items
Parameters
Description
Output
Signal
PPS3
IRIG-B3
PPM
PPH
Set output signal type for O3.
PPS3: Set output signal is PPS;
IRIG-B3: Set output signal is IRIG-B;
PPM: Set output signal is PPM;
PPH: Set output signal is PPH.
The PPS, PPM and PPH are pulse signal. The interval is per
second, per minute and per hour sending one pulse.
Second
Compensation
0s
Set second compensation offset for O3
Unit is second(s);
Range is between -999999999s and 999999999s.
Default value is 0s.
PPS
Compensation
0ns
Set PPS compensation offset for O3
Unit is nanosecond(ns);
Range is between -250000000ns and 250000000ns.
Default value is 0ns.
IRIG-B
Time
Format
UTC
TAI
Local
Set reference time for IRIG-B output signal of O3
UTC: Make output time working at UTC format;
TAI: Make output time working at TAI format.
Local: Make output time working at Local format.
IRIG-B
Mode
Even
Odd
Set IRIG-B check code for O3.
Even: Use Even mode check code to code IRIG-B signal;
Odd: Use Odd mode check code to code IRIG-B signal.
IRIG-B
+
Set IRIG-B output signal polarity for O3.