KwiKool BioKool KBIO1411 Operation Manual Download Page 26

Start by going to 

SETTINGS

. Use 

FAN

 and 

MODE

 to scroll. 

Use the 

UP

 and 

DOWN

 arrows to change values.

Hold 

MODE

 until it beeps and flashes a lock icon, then hold 

FAN

 until it 

beeps. Release 

FAN

 then touch it again, it will beep and then display 

P04.

To scroll use 

FAN

 and 

MODE

. Select 

ON/OFF

 to exit, or after

 one

 minute the 

display defaults to the operating screen. Use the 

UP

 and 

DOWN

 arrows to 

change values.

SETTING USER SETTINGS

SETTING FOR YOUR TECHNICAL STAFF

Enter this mode by short pressing the         icon.

USER PARAMETERS

Summary of Contents for BioKool KBIO1411

Page 1: ...th Care Environments KBIO1411 AIR COOLED KWBIO1411 WATER COOLED Stainless Steel Commercial Strength Hepa Filtration Ultraviolet Irradiation 13 800 BTUH 1 Ton 115V 15 Amp Standard UV LIGHT HEPA FILTER...

Page 2: ...FAMILY OF PRODUCTS...

Page 3: ...potentially explosive combustible or corrosive gaseous atmosphere DO NOT move the system while it is operating Before moving first turn the system OFF and unplug it from the power source Lastly unloc...

Page 4: ...or evaporator coil freezing FILTERED DILUTED COOLED BioKool s exclusive four point air therapy process cools cleans disinfects and retards mold and microbe growth IRRIDIATED According to the CDC hospi...

Page 5: ...is the only portable air conditioner specially designed to perform air therapy for regulation in sensitive health care facilities Biokool is enginee red with the highest filtration in the world known...

Page 6: ...reduce the potential for cross contamination KwiKool Biokool is the new benchmark for supplemental hygienic air conditioningthatcanliveuptotheexceptionalanduncompromisingstandards required inside of m...

Page 7: ...nser Water Inlet Condenser Water Outlet Sight Glass Remove Cover Condensate Alarm Jack Condensate Nipple H P Reset Switch Condensate Alarm Jack H P Service Port L P Service Port 1 2 3 4 5 6 7 8 9 10 1...

Page 8: ...essure Switch Non CFC Refrigerant Supply Air Chute Data Op onal Power Consump on kW Power Cord Gauge Length in Feet Evaporator Freeze up Condensate Pump Over ow Recommended Breaker Size BTU hr 95 F at...

Page 9: ...rol Cold Air Return Access Door KoolPad Digital Control Cold Air Supply Condenser Air Inlet Condenser Air Outlet Storage Pocket Power Cord Condensate Alarm Jack Condensate Nipple H P Reset Switch Low...

Page 10: ...e Switch Fan Motor Overload Compressor Short Cycle Automa c Restart Condensate Pump Safety Cut o Low Pressure Switch Non CFC Refrigerant Supply Air Chute Data Op onal I O Integral Condenser In Out Pow...

Page 11: ...r outlet on the back of your KwiKool and connect the discharge end of the tube to the barbed connec tor on the condensate tank The condensate float jack must be inserted into the female condensate jac...

Page 12: ...s exclusive IO integral condenser system isolates both the condenser discharge air and the condenser make up air from the conditioned space The ceiling kit is comprised of flanges with foam tape faste...

Page 13: ...P reset button located in the return air compartment be sure the water supply has been re es tablished to avoid future tripping For long term use of water cooled models a circulating water supply such...

Page 14: ...ter until the water is clear Note Before reinstalling the filter ensure that the pre filter is completely dry Typically a safe waiting time is three hours This time will vary depending on conditions s...

Page 15: ...VERAGE FILTER 8 MICRONS RED BLOOD CELL 3 MICRONS BACTERIA SIZE Common standards require that a HEPA air filter must remove 99 9 of particles greater than or equal to 0 3 m diameter PATENT PENDING 99 9...

Page 16: ...correct direction before securing it in the housing The black rubber faces towards the interior of the unit Using the lip on the filter pull the HEPA filter straight out Gently loosen the two screws o...

Page 17: ...disposable and therefore must be periodically inspected and replaced based on the air quality of your conditioned space Encased in steel HEPA filters measure 21 X 13 5 X 4 inches and are lined with fi...

Page 18: ...ria and viruses by altering the structure and the molecular bonds of their DNS after UVC exposure the organism dies off leaving no offspring and the remaining population of the microorganism diminishe...

Page 19: ...ces with which it comes into contact Excessive exposure to UV radia on can result in acute and chronic harmful e ects on the eye s dioptric system and re na Max Voltage 210 Volts Max Wattage 85 Watts...

Page 20: ...ea ng the steps to secure it with the installed door latches Push the front panel closed and ghten the screws un l they are rmly secured Reach inside the unit and push the bulb up before pulling it ou...

Page 21: ...ultra violet light inside the air chamber Germicidal UV is a highly effective method of destroying microorganisms Internal UVC light further reduces microorganisms by irradiating the evaporator coil...

Page 22: ...e button on the switch located on the compressor discharge line If the switch has tripped you will feel a distinct click upon reset Standard KwiKool KPO models are not designed to operate at temperatu...

Page 23: ...start cooling if the set point is under room temperature To operate the control press the ON OFF icon A short press on this button turns the system on or off and the systems operates in the last para...

Page 24: ...l operate only while the compressor is on In MANUAL FAN mode the supply air fan is on and the fan icon will not display The supply air will operate at all times when the system is on A light tap on th...

Page 25: ...OFF manually will turn the evaporator fan off also impe ding the BioKool from restarting automatically In FAN mode the supply air fan and UV lights shut down when OFF is selected The hot air exhaust...

Page 26: ...FAN until it beeps Release FAN then touch it again it will beep and then display P04 To scroll use FAN and MODE Select ON OFF to exit or after one minute the display defaults to the operating screen U...

Page 27: ...es a manual reset after corrective action is taken the reset switch is located in the power cord pocket Push in to reset if activa ted you will hear a click If this alarm is engaged the system will no...

Page 28: ...condensate outlet KwiKool condensate pumps are equipped with a pump safety cut off that prevents accidental water overflow by shutting your KwiKool down and alerting operators with an audible alarm a...

Page 29: ...or 1 0 Unlock 1 Lock 0 Unlock 1 Lock 0 Unlock 1 Lock 0 Unlock 1 Lock A1 CP LP Customer Installed input Condensate Fault Pump Low Freon Level Detected Optional Standard Standard HP FL FS High Pressure...

Page 30: ...AMETERS P30 P40 P41 P42 P100 P101 P102 P105 P106 P107 P108 Enable Dimming Dimming Time Dimming Brightness ActiveStateBrightness UV Light Time UV Light Actual Time UV Light Reset Settings Hours 100 Hou...

Page 31: ...KWIKOOL if the problem persist Unit Displays HP Audio alarm is sounding during start up or while opera ng Microprocessor board has detected high pressure The High Pressure switch is likely tripped Hi...

Page 32: ...cle add another KwiKool system or larger capacity model close evaporator compartment door inspect supply air blower for worn condi on or breaking Install service gauges to view pressures Control Box C...

Page 33: ...ter and replace if dirty Make sure nothing is blocking the lter inlet Check for icing on coil Resets automa cally when fault condi on is corrected System is ON and ashing F or C The microproces sor re...

Page 34: ...1 800 KWIKOOL 594 5665 sales kwikool com KWIKOOL Manufactures Excellent Commercial Portable Cooling Equipment IN THE U S A Manufacturing Excellence PATENT PENDING...

Reviews: