DDR OT/BACIP Gateway
DDRA 015 v1.1 04/2010
18
Analogue Input Overview
BACnet control mode (Manual)
This feature is enabled when AO-1 is set to 1
(BACnet control), the gateway will ignore the
thermostat (if connected) and communicate
directly with the boiler. The Control Set-point will
now determine the boiler target temperature. The
gateway no longer retrieves any values from the
thermostat, these object will change to a value of
-99.
Temperature Units
You have the ability to control whether
temperatures are displayed in Celsius or
Fahrenheit by setting AO-2 (Analog Output 2).
This will also determine whether the Control Set-
point (AO-3) is provided in
⁰
C or
⁰
F.
BACnet Objects
BACnet Object
Description
Units
Source
Analog Input 1
Boiler Set-point
⁰
C /
⁰
F
T / M
Analog Input 2
Boiler water temperature
⁰
C /
⁰
F
B
Analog Input 3
Maximum Modulation level
%
T
Analog Input 4
Current Modulation level (boiler modulation)
%
B
Analog Input 5
Room Temperature
⁰
C /
⁰
F
T
Analog Input 6
Room Set-point temperature
⁰
C /
⁰
F
T
Analog Input 7
Outside Temperature
⁰
C /
⁰
F
T
Analog Input 8
Return Water Temperature
⁰
C /
⁰
F
B
Analog Input 9
Flue Gas Temperature
⁰
C /
⁰
F
B
Analog Input 10
Boiler Heat Exchanger Temperature
⁰
C /
⁰
F
B
Analog Input 11
Boiler Fan Speed
Hertz
B
Analog Input 12
Water Pressure
Bar / PSI
B
Analog Input 13
OEM Fault Code
0-255
B
Analog Input 14
OEM Diagnostic Code
0 - 65535
B
Binary Input 1
Boiler Fault (no fault / fault)
0/1
B
Binary Input 2
Flame Status (no flame / flame)
0/1
B
Binary Input 3
Fault - Service Required (not req'd / req'd)
0/1
B
Binary Input 4
Fault - Lockout Reset
0/1
B
Binary Input 5
Fault - Low Water Pressure
0/1
B
Binary Input 6
Fault - Gas / Flame
0/1
B
Binary Input 7
Fault - Air Pressure
0/1
B
Binary Input 8
Fault - Water Over-Temperature
0/1
B
Analog Output 1
Control source (Setpoint from Thermostat or Manual)
0/1
Analog Output 2
Temperature Units (
⁰
C /
⁰
F)
0/1
Analog Output 3
Control Set-point (only if control source is Manual)
⁰
C /
⁰
F
Analog Output 4
Control Method (Setpoint / Modulation Controlled)
0/1
T=Thermostat B=boiler M=Manual (BACnet)
Temperature units displayed / Set-point units, is determined by Analog Output 2