- 16 -
R410A pressure and temperature mapping table
7. Malfunction and Troubleshooting
7.1 Error code on controller
Malfunction
Error
code
Reason
Solution
Low ambient
temperature
protection
PP0
Ambient temperature
is too low
Inlet water
temperature sensor
failure
PP1
The sensor in open or
short circuit
Check or change
the sensor
Outlet water
temperature sensor
failure
PP2
The sensor in open or
short circuit
Check or change
the sensor
Heating condenser
sensor failure
PP3
The sensor in open or
short circuit
Check or change
the sensor
Gas return sensor
failure
PP4
The sensor in open or
short circuit
Check or change
the sensor
Ambient
temperature sensor
failure
PP5
The sensor in open or
short circuit
Check or change
the sensor
Temperature
difference too
much protection
water inlet and
outlet
PP6
Water flow volume is
not enough
Check the water
flow volume or
water jammed
or not.
Unit
Condition
Power Off
Running
Ambient
(
℃
)
-5~5
5~15
15~2
5
25~3
5
/
/
/
/
/
Water
temp (
℃
)
/
/
/
/
10~
15
15~
20
20~
25
25~
30
30~
35
Pressure
gauge
(kg/cm2)
6.8~
9.3
9.3~
12.5
12.5
~16.
4
16.4
~21
13~
18
15~
19
16~
23
19~
28
21~
35
Summary of Contents for Green Energy ECO 10
Page 2: ......
Page 22: ...20 8 Electrical Wiring ECO 3 5 8 10 wiring diagram...
Page 23: ...21 ECO 12 wiring diagram...
Page 24: ...22 9 Figures of the pump 9 1 Exploded Diagram...
Page 27: ...25 11 Warranty and Returns 11 1 Warranty...
Page 49: ...47 8 Verkabelung ECO 3 5 8 10...
Page 50: ...48 ECO 12...
Page 51: ...49 9 Fakten zur Pumpe 9 1 Explodierte Zeichnung...
Page 57: ......
Page 58: ...A0111KWDE01...