E-6
English
5
5 Set-up
5.1 General
The unit must be installed indoors on a level, smooth and hori-
zontal surface. The entire base of the frame should lie directly on
the floor to ensure a good soundproof seal. If this is not the case,
additional sound insulation measures may be necessary. Instal-
lation on top of a customer-supplied foundation requires a sur-
face that fully supports the base. The heat pump must be in-
stalled in a way that allows maintenance work to be carried out
without hindrance. This can be ensured by maintaining a clear-
ance of 1 m in front and to the left and right of the swimming pool
heat pump.
Never install the device in rooms subject to high humidity. Con-
densation can form on the heat pump and air circuit if the humid-
ity exceeds 50% and the external temperature is below 0 °C.
If the swimming pool heat pump is installed on an upper floor, the
load-bearing capacity of the ceiling should be checked. On ac-
count of the acoustics, measures for isolating possible vibrations
should also be very carefully planned. Installation on wooden
floors is not recommended.
5.2 Condensed Water Pipe
Condensed water that forms during operation must be drained
off frost free. To ensure proper drainage, the swimming pool heat
pump must be mounted horizontally. The condensed water pipe
must have a minimum diameter of 50 mm and should be fed
frost-proof into a sewer. Condensate should not be discharged
directly into clearing tanks and cesspits because the aggressive
vapours could destroy the evaporator. The use of a siphon is
therefore recommended.
5.3 Sound
To prevent solid-borne sound from being transmitted to the pool
water system, we recommend use of a flexible hose to connect
the swimming pool heat pump to the pool water system.
Installed air ducts should be sound-isolated from the swimming
pool heat pump to prevent the transmission of solid-borne sound
to the ducts.
6 Installation
6.1 General
The following connections need to be established on the heat
pump:
Fresh and exhaust air
Flow and return flow of the pool water
Condensate outflow
Power supply
Control line to remote control
Control line to on-site release contact (floating)
6.2 Air Connection
ATTENTION!
Do not restrict or block the area around the air intake or outlet.
ATTENTION!
Only operate the heat pump with the air ducts connected.
The glass fibre reinforced concrete air ducts offered as accesso-
ries are moisture-resistant and diffusion-free.
The sealing collar is used to seal the air ducts on the swimming
pool heat pump. The air ducts are not screwed directly onto the
swimming pool heat pump. When installed, only the rubber seal
comes into direct contact with the swimming pool heat pump.
This guarantees easy assembly and disassembly of the heat
pump and also ensures that solid-borne sound is well insulated.
If another type of air duct is used, observe the external and inter-
nal dimensions as specified in the figure. Also ensure that the vi-
bration and duct insulation are adequate.
If flange-mounted air ducts are used, connecting stubs are se-
cured on the air inlet and air outlet sides of the evaporator with 4
M8 x 16 hexagon bolts in the threaded holes provided. When
doing this, ensure that both air duct stubs only touch the insula-
tion. There should be no contact with the external sheeting.
P
P
P
P