6
EA350
2. Allow approximately 3 seconds before removing
the battery.
3. With the voltage regulator disconnected ( wires 3
and 4 ), start the prime mover and measure the
“ residual ” voltage available at the auxiliary
winding. If this voltage is greater than 5 VAC,
reconnect voltage regulator, and voltage build-up
should be successful. If less than 5 VAC is
measured, repeat field flashing procedure.
4. If residual voltage is greater than 5VAC, but AVR
still unable to build up voltage, please replace
with another AVR.
WARNING
Please make sure you have read and
understand the contents of the instruction
manual prior to installation. Incorrect wiring
connection may result in irreversible damage
to the product and other equipments.
This Automatic Voltage Regulator is not
equipped
with
loss-Sensing
Protection
function / Over Excitation Protection. An
additional Over-Voltage Protection device for
load may be required to avoid possible
damage to the equipment or severe personal
injury or death.