background image

 
 

______________________________________________________________________________________ 

4

 

EA350

 

50

55

60

65

70

0

10

20

30

40

50

60

70

80

90

100

GENERATOR OUT

PUT(%F

RO

M NO

RMIN

AL

)

FREQUENCY (HZ)

50 HZ CURVE

60HZ CURVE

5

10

15

20

25

30

35

40

45

●  The EA350 has the roll-off point preset to 58 Hz 

in the 60 Hz mode and 48 Hz in the 50 Hz mode. 
To change the roll-off point, adjust engine speed 
to the desired rated speed. (50 or 60 Hz). 

●  Set  the  voltage  to  the  desired  setting  at  rated 

speed. Adjust engine speed to the desired roll-off 
point.  Turn  the  potentiometer  counterclockwise 
until the voltage starts to drop off. Then adjust the 
potentiometer clockwise  until the  voltage returns 
to rated voltage. Re-adjust engine speed to rated 
speed. 

2.6  Corner Frequency Jumper 

Regulator  are  delivered  with  the  Corner  Frequency 
Jumper  set  for  60  hertz  operation.  This  gives  a 
corner frequency of 55 hertz. For 50 hertz operation 
and  a  corner  frequency  of  45  hertz,  the  Corner 
Frequency  Jumper  must  be  moved  to  the  50  Hz 
terminal. 

2.7  Voltage Adjust Rheostat Jumper 

●  Rheostat  Jumper  connected  across  terminals  6 

and 7. This enables adjustment of the generator 
output  voltage  rheostat.  A  1000  ohm,  half-watt 
rheostat 

will 

provide 

adequate 

voltage 

adjustment  range  for  most  applications.  Figure 
5~6 

shows 

the 

proper 

remote 

rheostat 

connections. 

●  The EA350 potentiometer controls are accessible 

through the controller front panel and are shown 
in Figure 2. 

2.8  Voltage Adjust Rheostat Jumper 

2P DIP switch on for 120Vac generator system 

2P DIP switch off for 240Vac generator system 

2.9  Stability Selection 

When  excitation  under  voltage,  it  can  result  in 
insufficient adjustment range for stability adjustment 
and when excitation over voltage, the response from 
the  AVR  becomes  sluggish.  The  AVR  is  equipped 
with  2  bridging  wires  J1  and  J2  to  help  improve  or 
relief the condition. See Figure 2. 

●  If  the  unloaded  excitation  voltage  is  less  than  7 

VDC, please cut open the J2 red bridging wires. 

●  If  the  unloaded  excitation  voltage  is  greater 

than25  VDC,  please  cut  open  the  J1  white 
bridging wires. 

 
 
 

 

FREQUENCY COMPENATION (See Figure 1) 

1. The frequency compensation characteristic of 

Figure 1 used to improve system load pickup 
performance  by  restraining  voltage  recovery 
until frequency has also started to recover. 

2. The regulator is shipped from the factory set 

at  a  45 

Hz  “corner  frequency”  for  50  Hz 

systems. For 60 Hz systems, a 55 Hz corner 
frequency  is  achieved  by  removing  the 
“50-50” external link.

 

3.  OPERATION PROCEDURE 

3.1  Operational Test 

Complete the following steps before proceeding with 
system start-up. 

1. Connect the Analog Voltage Controller as shown 

in the operational test diagram of Figure 8. Do not 
apply power. Ensure that the light bulbs are rated 
for  120  volts  and  less  than  100  watts.  Figure  4. 
Operational Test Diagram. 

2. Adjust the Regulator voltage adjust potentiometer 

and remote voltage adjust rheostat (if used) fully 
counterclockwise. 

3. Apply  240  VAC,  60  Hz  power  to  the  controller. 

The light bulbs should flash momentarily. 

4. 

Slowly  adjust  the  controller’s  voltage  adjust 

potentiometer clockwise. 

RESULT :

 

1. Before  minimum  luminance  is  reached,  the  light 

bulbs  should  attain  maximum  luminance  to 
signify the regulation point. 

2.  At  the  regulation  point,  a  small  change  in  the 

voltage adjust potentiometer or rheostat position 
should turn the light bulbs on or off.

 

Figure 3    Frequency Compensation Curves 

Summary of Contents for EA350

Page 1: ... St Qianzhen Dist Kaohsiung City 80664 Taiwan Tel 886 7 8121771 Fax 886 7 8121775 URL http www kutai com tw Self Excited Automatic Voltage Regulator For General Generators Compatible with Marathon SE350 Use for reference purpose only and not a genuine Marathon product EN61204 3 2001 certified ...

Page 2: ...terminal 5 VAC Operating Temperature 40 C 60 C Storage Temperature 65 C 85 C Burden 250 500VA Max External Volts Adjustment 5 with 1K ohm 1 watt trimmer 10 with 2K ohm 1 watt trimmer EMI Suppression Internal electromagnetic interference filtering Unit Power Dissipation Max 8 watt Under Frequency Protection Factory Setting 60 Hz system presets knee point at 54 61 Hz 50 Hz system presets knee point ...

Page 3: ... For 5 voltage variation use a 1000 ohm 1 2 watt rheostat See Figure 5 6 2 4 Stability Adjustment System stability is the ability of the generator to respond to load transients Decreasing the stability makes the generator less sluggish and faster to respond to toad transients If the stability of the regulator is decreased too much the generator will tend to hunt under steady state Conditions the s...

Page 4: ...ion under voltage it can result in insufficient adjustment range for stability adjustment and when excitation over voltage the response from the AVR becomes sluggish The AVR is equipped with 2 bridging wires J1 and J2 to help improve or relief the condition See Figure 2 If the unloaded excitation voltage is less than 7 VDC please cut open the J2 red bridging wires If the unloaded excitation voltag...

Page 5: ...ive load or a short circuit 2 If a minimal residual of 5 volts is not present perform the steps under Field Flashing Apply and remove the generator load to verify stability If the generator responds too slowly or hunts oscillates Check the generator output for excessive load or a short circuit Adjust the Regulator stability control with no load applied Check the stability of the governor system Ch...

Page 6: ...eater than 5VAC but AVR still unable to build up voltage please replace with another AVR WARNING Please make sure you have read and understand the contents of the instruction manual prior to installation Incorrect wiring connection may result in irreversible damage to the product and other equipments This Automatic Voltage Regulator is not equipped with loss Sensing Protection function Over Excita...

Reviews: