___________________________________________________________________________________________
2
ADVR-250
Figure 1
Outline Drawing
SECTION 1 : SPECIFICATION
Sensing Input ( 0V, 110V ) Average Reading
Under Frequency Protection (Factory Presets)
Voltage
85
140 Vac, 1 phase 2 wire
50 Hz system knee point at 48 Hz
Frequency
50/60 Hz, Potentiometer setting
60 Hz system knee point at 58 Hz
Excitation Output ( E+, E- )
Over Excitation Current Limiting
120V 1 phase Continuous
63 Vdc
3.5A
Excitation Current 5 A +/- 10 %
Max. 110 Vdc 5A for 10 secs.
Resistance
Min. 18 ohms, Max.100 ohms
Voltage Thermal Drift
Fuse Spec.
Slow blow 5 x 20mm 8A
Less than 3% at temperature range -40 to +70
˚C
External Voltage Adjustment (1K ohm )
Under Frequency Knee Point Thermal Drift
Max.+/- 14% @ 1 K ohm 1 watt potentiometer
Less than +/- 0.1 Hz at -40 to
+70 ˚C
Voltage Regulation
Environment
Less than +/- 0.5% (with 4% engine governing)
Operating Temperature -40 to
+70 ˚C
Storage Temperature
-40 to
+85 ˚C
Build Up Voltage
Relative Humidity
Max. 95%
5 Vac 25 Hz residual volts at power input terminal
Vibration
5.5 Gs @ 60 Hz
Soft start ramp time
Dimensions
3 s/- 10%
140.0 (L) x 81.0 (W) x 46.0 (H) mm
5.51 (L) x 3.19 (W) x 1.81 (H) inch
Typical System Response
Less than 20 milliseconds
Weight
300 g +/- 2%
EMI Suppression
0.66 lb +/- 2%
Internal electromagnetic interference filtering
Static Power Dissipation
Max. 4 watts
SECTION 2 : APPEARANCE / DIMENSIONS / INSTALLATION DRAWING
Unit : mm
[inch]
[3.19"]
81.0
[5.51"]
140.0
[4.53"]
115.0
[1.06"]
27.0
[1.96"]
50.0
[1.81"]
46.0
M4 L25
8.5
[0.33"]
Connection Terminals
:
6.35 mm (1/4 inch)
Flag Terminals
( “Fast-On” terminals ).