ADVR-250

 

SECTION  4  :  U/F  PROTECTION  &  LAM 
FUNCTION SELECTION 

 
The Under Frequency Protection (U/F) and LAM 
function can be selected using the potentiometer. 

4

3

2

1

SPECIAL

65Hz

57Hz

KNEE

KNEE

KNEE

5

6

7

8

9

0

0 1

2

3

4

5

6

7

8

9

60Hz

50Hz

 

Figure 3 

 
 

ATTENTION 

The  potentiometer  settings  must  correspond  to 
the  rated  frequency.  An  error  in  settings  could 
cause damage to the generator.

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

50 Hz Systems 

0

 Under Frequency knee point 48 Hz, LAM function 

“OFF”. Use when transient loads are below 40% of 
rated generator capacity. 

1

 Under Frequency knee point 48 Hz, LAM function 

set  to  (13%),  Use  when  transient  loads  are 
between 40 

– 70% of rated generator capacity. 

2

 Under Frequency knee point 48 Hz, LAM function 

set to (25%). Use when transient loads are greater 
than 70% of rated generator capacity. 

 

60 Hz Systems 

3

 Under Frequency knee point 58 Hz, LAM function 

“OFF”. Use when transient loads are below 40% of 
rated generator capacity. 

4

 Under Frequency knee point 58 Hz, LAM function 

set  to  (13%),  Use  when  transient  loads  are 
between 40 

– 70% of rated generator capacity. 

5

 Under Frequency knee point 58 Hz, LAM function 

set to (25%). Use when transient loads are greater 
than 70% of rated generator capacity. 

 

Special Systems 

6

 Under  frequency  knee  point  57  Hz,  LAM  function 

“OFF”. Under a load, engine speed variations can 
be greater than 2 Hz. 

7

 Under  frequency  knee  point  65  Hz,  LAM  function 

“OFF”. 

8

 Factory setting of the Under Frequency knee point 

is  48  Hz  and  LAM  function 

“OFF”.  This  option  is 

supplied  for  special  projects,  which  must  be 
ordered separately and are set at the factory. 

9

 Under frequency knee point 47.5 Hz

LAM function 

“OFF”. Under a load, engine speed variations can 
be greater than 2 Hz. 

 
 

Summary of Contents for ADVR-250

Page 1: ...aiwan ADVR 250 Generator Automatic Voltage Regulator Operation Manual Analog Digital Single phase detection Excitation Current 3 5 Amps For use in brushless self excited shunt generators Compatible with Leroy Somer R250 R230 AVR All manufacturer names and numbers are used for reference purpose only and do not imply that any part is the product of these manufacturer ...

Page 2: ... Adjustment 1K ohm Under Frequency Knee Point Thermal Drift Max 14 1 K ohm 1 watt potentiometer Less than 0 1 Hz at 40 to 70 C Voltage Regulation Environment Less than 0 5 with 4 engine governing Operating Temperature 40 to 70 C Storage Temperature 40 to 85 C Build Up Voltage Relative Humidity Max 95 5 Vac 25 Hz residual volts at power input terminal Vibration 5 5 Gs 60 Hz Soft start ramp time Dim...

Page 3: ...e and engine speed fluctuates In order to reduce the level of volatility after a load is added the engine speed will slow lowering the total power output of the generator and delaying recovery The low frequency knee point setting should be below a nominal setting for 2 Hz to cause the output voltage and engine speed to have a smooth recovery The LAM function allows choice of reduction settings of ...

Page 4: ... function set to 25 Use when transient loads are greater than 70 of rated generator capacity 60 Hz Systems 3 Under Frequency knee point 58 Hz LAM function OFF Use when transient loads are below 40 of rated generator capacity 4 Under Frequency knee point 58 Hz LAM function set to 13 Use when transient loads are between 40 70 of rated generator capacity 5 Under Frequency knee point 58 Hz LAM functio...

Page 5: ...e 5 ATTENTION 1 Before using a Megger or a Withstand Voltage Tester removes the wires connecting to the AVR to prevent high voltage damage to the regulator 2 Improper setting of under frequency protection could cause the output voltage of the unit to drop or become unstable under with changes in load Avoid making any changes to the U F setting unless necessary Use only replacement fuses specified ...