XPS-E
8 / 36
By executing the following steps, the XPS-E Gateway can be set into
operation:
◦ Connect XPS-E to PROFIBUS by using a standard PROFIBUS cable
with corresponding D-SUB PROFIBUS connector. For the connector
assignment please refer to chapter „Connector Assignment and Cabling
[
}
27]“ and follow the Installation Guidelines for PROFIBUS (No. 2.112,
PNO).
◦ Connect the serial end device with XPS-E
◦ Check your PROFIBUS network with regard to an unused Slave
address and adjust this free address at the coding switch of XPS-E.
◦ Plug in the power supply. The power supply of the XPS-E is connected
by spring clips at the front side.
ð
As soon as the device is powered, the Status/Busfail LED is flashing
red.
NOTICE
The Status/Busfail LED is flashing red until the device is
parameterized and configured
In this status, no data exchange can take place (neither send nor receive).
Only after successful parameterization and configuration the Status/Run
LED is flashing green. Now, the device is ready for data exchange.
3.2 Test the PROFIBUS connection
If you have a PROFIBUS-DP configuration tool, you can test the
PROFIBUS connection to the XPS-E Gateway. For this purpose,
load the deliverable GSD file into your configuration tool.
The DP Master shall now configure XPS-E. If this configuration is
successful, the Status/Run LED is flashing green.
If you do not have a PROFIBUS-DP configuration tool or if you wish
to change the pre-defined parameters (User_Prm_Data) in the GSD
file, please refer to the following chapters for the parameterization.
Put into operation