8 Technical Data
PROFIBUS-DP-Interface
Transmission protocol
PROFIBUS-DP acc. to EN50170-3
Slave coupler
Transmission rates
9.6Kbit/s, 19.2Kbit/s, 93.75Kbit/s, 187.5Kbit/s,
500Kbit/s, 1.5Mbit/s, 3Mbit/s, 6Mbit/s, 12Mbit/s,
automatic adjustment
Potential segregation:
Opto-coupler interface and DC/DC transducer
Isolation voltage U>500V
Terminator
TYP A
Operating modes
Sync_Req and Freeze_Req are not supported.
Addressing
1 - 99 Sync_Req and Freeze_Req are not sup-
ported.
Ident-Number
0x9510
Parametrization data:
23 Byte ( 16 Byte User Parameter)
Diagnostic information
6 Byte system diagnostics acc. to standard
8 Byte device-specific diagnostics
Data_Exchange Buffer
4 - 240 Byte I/O selectable (3 Bytes with
header functionality).
RS232-Interface
Interface
RS232 interface with Handshake signals (RTS,
CTS).
RS422/485 interface with Handshake signals
(CONTROL, INDICATION).
Interface physics can be adjusted via
PROFIBUS by means of User_Parameter.
Transmission rates
150bit/s, 300bit/s, 600bit/s, 1.200bit/s, 2.400bit/
s,4.800bit/s, 9.600bit/s, 19.200bit/s
Character Transmission
8N1, 7N2, 7E1, 7O1
Handshake
HW (RTS/CTS, CONTROL/INDICATION),
SW(XON/XOFF), no
XOFF Timeout
adjustable to max. 25,5 seconds
Data transmission modes Poll mode, Request mode, serial triggered
mode
Receive buffer
2 KByte
Potential segregation
optional
Connection
Power Supply
2-pin spring clip 2,5mm
2 without ferrule 1,5mm
2 with ferrule
PROFIBUS-DP
9-pin female D-SUB (DIN 41652)
RS-Port
9-pin male D-SUB (DIN 41652)
Technical Data