![Kuhnke FIO (V2) Manual Download Page 110](http://html.mh-extra.com/html/kuhnke/fio-v2/fio-v2_manual_2009572110.webp)
Kendrion Kuhnke Automation GmbH
AI4-I
110
11/25/2016
0-20mA (6)
2000, 2
Input 1
UINT8
Off
Off (0),
4-20mA (5),
0-20mA (6)
RW
2000, 3
Input 2
UINT8
Off
Off (0),
4-20mA (5),
0-20mA (6)
RW
2000, 4
Input 3
UINT8
Off
Off (0),
4-20mA (5),
0-20mA (6)
RW
2003
Input Average
Array
2003, 0
Number of Entries
UINT8
4
RO
2003, 1
Input 0 Average
UINT8
1
1..255
RW
2003, 2
Input 1 Average
UINT8
1
1..255
RW
2003, 3
Input 2 Average
UINT8
1
1..255
RW
2003, 4
Input 3 Average
UINT8
1
1..255
RW
6401
Analog Input
Array
6401, 0
Number of Entries
UINT8
4
RO
6401, 1
Analog Input 0
UINT16
RO P
6401, 2
Analog Input 1
UINT16
RO P
6401, 3
Analog Input 2
UINT16
RO P
6401, 4
Analog Input 3
UINT16
RO P
6500
StateWord
Array
6500, 0
Number of Entries
UINT8
32
RO
6500, 1
ResetErrorAck
BOOL
RO P
6500, 2
Undervoltage24
BOOL
RO P
6500, 3
EtherCAT Error
BOOL
RO P
6500, 4
ConfigError
BOOL
RO P
6500, 5..8
-
BOOL
RO P
6500, 9
Input 0 low
BOOL
RO P
6500, 10
Input 1 low
BOOL
RO P
6500, 11
Input 2 low
BOOL
RO P
6500, 12
Input 3 low
BOOL
RO P
6500, 13..16 -
BOOL
RO P
6500, 17
Input 0 high
BOOL
RO P
6500, 18
Input 1 high
BOOL
RO P
6500, 19
Input 2 high
BOOL
RO P
6500, 20
Input 3 high
BOOL
RO P
6500, 21..32 -
BOOL
RO P
6500, 1
ResetErrorAck
BOOL
RO P
6500, 3
EtherCAT Error
BOOL
RO P
6500, 4
ConfigError
BOOL
RO P
7001
Module Control
Array
7001, 0
Number of Entries
UINT8
1
RO
7001, 1
Reset Error
BOOL
RW P
RO=Read only, RW= Read/Write, P=Process image