Kendrion Kuhnke Automation GmbH
AI4-I
108
11/25/2016
For information and settings Service data objects are designed.
Settings for the AI4-I 12Bit-module, such as the properties of the individual inputs can be made in the
configurator already offline. These are then executed by the EtherCAT master at startup.
It is also possible to make adjustments during runtime by executing the SDO transfer blocks of the EtherCAT
master control.
Press the button "Hinzufügen…", select the object and set the desired value.
4.19.4.5 Options
The following options can be set:
Name
Value
Explanation
InputProperties
0
Off (default)
5
4-20mA
6
0-20mA
Average
n=1..255
Inputn= = Average after n cycles (default=1)