ORIGINAL OPERATING INSTRUCTIONS
Commissioning
11/15/2016
39/150
7.6
Configuration of drive signal
The drive signal has to be configured before the control system is put into operation:
Hinweis
For the correct configuration of the drive signal, the carrier vehicle must fulfill the
following conditions:
•
Square wave signal
•
Pulse-Pause max. 20%
•
min. 4 imp/m
•
Voltage swing min. 4 V
•
max. 1 kHz
Various possibilities for configuration:
•
Chapter
7.6.1 "Drive signal teach in", page 40
•
Chapter
7.6.2 "Manual entry of drive signal ", page 41
•
Chapter
7.6.3 "Drive signal over certain distance", page 42
1
Open user menu (see Chapter
)
2
Open detail menu (see Chapter
)
3
Turn left turning knob
➯
4
Confirm