8
5.2.13 Duration of the timed signal of output 2
(only if a timed signal has been
programmed in 5.2.12)
The duration can be set be-
tween 0.01 sec. and 99.99 sec.
A 0.00 setting is not accepted
5.2.14 End of programming
Programming is carried out
once more. The values input
can be checked and modified.
Programming is complete and
the values input are taken over
as new parameters.
Then the device is ready for op-
eration.
5.3 Speed indicator / frequency meter mode
setting
In the speed indicator / frequency meter mode, in-
puts INP B, RESET and GATE have no function.
Permanent signal
of output 2,
will become passive at count
value
preset 2 in adding
mode and at count value
0 in
subtracting mode
Timed signal
of output 2 will
become passive at count value
preset 2 in adding mode and
at count value
0 in subtract-
ing mode
Timed signal
of output 2 is ac-
tivated at count value
preset
2 in adding mode and at count
value
0 in subtracting mode
5.3.3 Setting of the scale factor
Scale factor setting range from
00.0001 to 99.9999. Fixed deci-
mal point set to 4 decimal
places.
A ”0” setting is not accepted.
5.3.4 Decimal point setting
The decimal point determines
the number of decimal places
displayed. It is only used for dis-
playing purposes and has no in-
fluence on the counting.
0
no decimal place
0.0
one decimal place
0.00
two decimal places
0.000
three decimal places
5.3.5 Display mode
Conversion and display of the
frequency / speed in 1/sec.
Conversion and display of the
frequency / speed in 1/min.
5.3.6 Maximum pulse waiting time
This value indicates the time during which the de-
vice will wait for a pulse before displaying a 0
speed.
Maximum delay 01.1 sec. (mini-
mum value)
Maximum delay 99.9 sec.
Values below 1.1 sec. are ignored and set auto-
matically to 1.1 sec.
5.3.1 Polarity of the inputs
npn: switching to 0 V
pnp: switching to +24 V
5.3.2 Activation of the 30 Hz filter
max. counting frequency: 20
kHz
max. counting frequency: 30 Hz