5.3 Speed indicator / frequency meter mode
setting
In the speed indicator / frequency meter mode, inputs
INP B, RESET and GATE have no function.
5.3.2 Activation of the 30 Hz filter
max. counting frequency: 20 kHz
max. counting frequency: 30 Hz
5.3.3 Setting of the scale factor
Scale factor setting range from 00.0001 to
99.9999. Fixed decimal point set to 4
decimal places.
A ”0” setting is not accepted.
5.3.4 Decimal point setting
The decimal point determines the number of
decimal places displayed. It is only used for
displaying purposes and has no influence on
the counting.
0
no decimal place
0.0
one decimal place
0.00
two decimal places
0.000
three decimal places
5.3.1 Polarity of the inputs
npn: switching to 0 V
pnp: switching to +24 V
5.3.6 Maximum pulse waiting time
This value indicates the time during which the device will wait for a
pulse before displaying a 0 speed.
Maximum delay 01.1 sec. (minimum
value)
Maximum delay 99.9 sec.
Values below 1.1 sec. are ignored and set automatically to 1.1 sec.
5.3.5 Display mode
Conversion and display of the frequency /
speed in 1/sec.
Conversion and display of the frequency /
speed in 1/min.
5.3.12 End of programming
Programming is carried out once more.
The values input can be checked and
modified.
Programming is complete and the values
input are taken over as new parameters.
Then the device is ready for operation.
5.3.8 Duration of the timed signal of the output
(only if
a timed signal has been programmed in 5.3.7)
The duration can be set between 0.01 sec.
and 99.99 sec.
A 0.00 setting is not accepted
5.3.7 Shape of output signal
Permanent signal.
Is activated at count
value
³
preset
Permanent signal.
Will become passive
at count value
³
preset
Timed signal.
Will become passive at
count value
³
preset
Timed signal.
Is activated at count value
³
preset