42
Appendix 1 Specifications
Model
HPM3340
200k
HPM3340
320k
HPM3340
400k
HPM3340
520k
Cabinet capacity
200kVA
180kW
320kVA
288kW
400kVA
360kW
520kVA
468kW
Module capacity
40kVA/36kW
Max. module number
5
8
13
Input
Phase
3 Phase 4 Wires and Ground
Rated Voltage
380/400/415Vac
Voltage Range
208~478Vac
Frequency Range
40Hz-70Hz
Power Factor
≥0.99
Current THDi
≤3%(100% nonlinear load)
Bypass Voltage
Range
Max.voltage:220V:+25%(op10%,+15%,+20%);
230V:+20%(op10%,+15%);
240V:+15%(op10%);
Min. voltage:-45%(optional -20%,-30%)
Frequency protection range: ±10%
Output
Phase
3 Phase 4 Wires and Ground
Rated Voltage
380/400/415Vac
Power Factor
0.9
Voltage Regulation
±1%
Frequency
Utility
Mode
±1%/±2%/±4%/±5%/±10%of the rated frequency(optional)
Battery
Mode
(50/60±0.1)Hz
Crest Factor
3:1
THD
≤2% with linear load
≤5% with non linear load
Battery
Voltage
±192V/±204V/±216V/±228V/±240VDC
(32 /34/36/38/40PCS)
Module charge
current(A)
max.
10A
Transfer Time
Utility to Battery : 0ms; Utility to bypass: 0ms
Protection
Overload
AC Mode
Load
≤110%: last 60min,≤125%: last 10min,≤150%: last
1min
,
≥150% shut down UPS immediately.
Bat. Mode
Load
≤110%: last 10min,≤125%: last 1min,≤150%: last
5s,
≥150% shut down UPS immediately.
Bypass
Mode
400A
500A
800A
Fuse Box
Input
100A
Battery
200A
Short Circuit
Hold Whole System