40
the overview of the SNMP card
NetAgent II-3Ports supports the Modem Dial-in(PPP) function to enable the remote control
via the internet when the network is unavailable .
In addition to the features of a standard NetAgent Mini, NetAgent II has the option to add
NetFeeler Lite to detect temperature, humidity, smoke and security sensors. Thus, making
NetAgent II a versatile management tool. NetAgent II also supports multiple languages and is
setup for web-based auto language detection .
Typical topology of the UPS Network Management
Relay card
A 10-pin terminal is supported to offer the signals of Bypass, Utility Failure, Inverter On,
Battery Low, UPS fault, UPS Alarm, and UPS Shutdown.
The relay communication card contains six dry contact outputs and one dry input. The inputs
and outputs are factory programmed according to functions listed in the table
Table:Relay Contacts (communication card)
Port
Function
1
Output
Utility Failure
2
/
3
Battery Low
4
On Bypass
5
UPS Fault
6
Inverter On
7
UPS Alarm
8
COM
9
Input
ON
10
OFF