KSR KUEBLER Betriebsanleitung Bypass-Magnetschalter
– BGU-...I
49
6
Faults
The most frequent causes for faults and the counter-
measures necessary are listed in the tables below.
Störung
Ursache
Maßnahme
Bypass mag-
netic switch can
not be attached
in the place in-
tended
Collision with other at-
tachments
Reconstruction of the
attachments or return to
factory
No signal or in-
correct signal
Electrical connection in-
correct
See Section 5.4 “Elec-
trical Connection”.
Check configuration
with the help of the cir-
cuit diagram.
Reed contact defective
Return to factory
incorrect switching be-
haviour
Change terminal config-
uration
Switch position incorrect
Re-position BGU
Cable ripped off
Return to factory
Switch is not triggered by
float
Return to factory
CAUTION!
Bodily injuries, property and environmental damages
If faults cannot be remedied with the help of the measures
listed above immediately decommission the device.
Ensure that there is no more pressure and protect
against accidental commissioning.
Contact the manufacturer.
In the event a return is necessary note the instruc-
tions in Section 8.2 “Return”.
Summary of Contents for BGU I Series
Page 47: ...KSR KUEBLER Betriebsanleitung Bypass Magnetschalter BGU I 47 Connection diagram...
Page 63: ...KSR KUEBLER Betriebsanleitung Bypass Magnetschalter BGU I 63...
Page 64: ...64 KSR KUEBLER Betriebsanleitung Bypass Magnetschalter BGU I...
Page 65: ...KSR KUEBLER Betriebsanleitung Bypass Magnetschalter BGU I 65...
Page 66: ...66 KSR KUEBLER Betriebsanleitung Bypass Magnetschalter BGU I...
Page 67: ...KSR KUEBLER Betriebsanleitung Bypass Magnetschalter BGU I 67...