EN
44
CONFIGURATION MENU (PC, MAC or APP)
In this paragraph all configuration parameters are described making reference to the configuration
interface from PC. However the same interface with the same lay-out is available using the APP, the
Ksenia SecureWeb or locally by means of the WebServer.
PARTITIONS
In this section it’s possible to configure the Partitions Descriptions and the 2 programmable arming
modes. Furthermore it is possible to configure the activation modalities of the Partitions related to the
2 programmable arming modes.
NOTE: the Disarm and Full Arm modes can not be modified.
CAMERAS
In this section you can configure up to 8 IP Cameras which will be activated in case of Alarm to en-
able screen-shots to be sent to the programmed recipients as email enclosures and/or Push Notifica-
tion.
MOTHER BOARD
Here you can configure all parameters associated to the mother board. It’s divided in 3 sub-sections:
1. Inputs
It’s possible to configure the Panel inputs (i1, i2, i3, i4) to which the wired sensors have to be linked.
The programmable Parameters for each input are the following:
Description: name associated to the input.
Partition: to which the sensors are associated. The factory default data are associating them to the first
partition (Doors and Windows).
Camera: is the camera associated to the Sensor, active in case of Alarm.
Input type: according to the linked Sensor, the way of processing the signal can be set-up as follows:
• Non Used: deactivated input
• Normally Closed: for an input linked to a normally closed type of Peripheral (e.g. Magnetic Contact,
not balanced Motion Detector, etc)
• Normally Open: for an input linked to a normally open Peripheral (e.g. Pushbutton)
• Double Balance: for inputs linked to a Peripheral with EOL resistors both on Alarm and tamper.
The Double Balance will be achieved using 10K Ohm Resistors in parallel or 4,7K in series.
• Low sensitivity Roller Blind: for input linked to Shutter Detector. Low Sensitivity in detection.
(7 pulses in 180 seconds).
• High sensitivity Roller Blind: for input linked to Shutter Detector. High Sensitivity detection.
(4 pulses in 180 seconds).
• Low sensitivity Inertial: for input linked to Break Detector. Low Sensitivity in detection.
(7 pulses in 30 seconds).
• High sensitivity Inertial: for input linked to Break Detector: High Sensitivity in detection.
(4 pulses in 30 seconds).
Delayed: enable this zone if you want this Sensor not to generate Alarms during the Entrance and Exit
Time.
Auto-bypassable: the Sensor will be automatically bypassed if during arming results violated. The Sen-
sor bypassing during the arming phase is totally transparent to the User and there will be no notifica-
tion to the Panel whatsoever, but it will be registered on the Event Log.
The auto-bypass function does not exclude any tamper.
The Sensor is automatically re-included by the next disarming.
Chime: if this option will be selected, when the Sensor is violated with Partitions armed, it generates a
voice message on the local Keypad (or remote if the KP is linked to the BUS) with Sensor Identification.
If the voice option is disabled, then it generates bips of 5 seconds each.
Always Activate: if this option will be selected, when the Sensor is violated an Alarm will be generated
regardless the arming of the relevant Partition.