![KSB WKTR Installation & Operating Manual Download Page 40](http://html1.mh-extra.com/html/ksb/wktr/wktr_installation-and-operating-manual_2006704040.webp)
CAUTION
Insufficient lubricating oil in the reservoir of the constant-level oiler
Damage to the bearings!
▷
Regularly check the oil level.
▷
Always fill the oil reservoir completely.
▷
Keep the oil reservoir properly filled at all times.
NOTE
When the pump is started up, the oil temperature in the bearing housing must not
below
the following value.
a) 10 °C / 50 °F (ISO-VG 32)
b) 15 °C / 59 °F (ISO-VG 46)
1
2
Fig. 10: Constant-level oiler
1
Constant-level oiler
2
Connection elbow of the constant-
level oiler
1. Hinge down the reservoir of the constant-level oiler (1).
2. Fill with oil through the open connection elbow.
3. Completely fill the reservoir of the constant-level oiler (1).
4. Snap the constant-level oiler (1) back into its operating position.
5. After approximately 5 minutes, check the oil level in the glass reservoir of
constant-level oiler (1).
The oil reservoir must be properly filled at all times to provide an optimum oil
level. Repeat steps 1 - 4, if necessary.
6. To check the function of the constant-level oiler (1), slowly drain oil via the
screwed plug until air bubbles develop in the reservoir.
6 Commissioning/Start-up/Shutdown
40 of 78
WKTR